MTV500ERP – Cod. 5454457
Timed power wireless dimmer
Functions
This module is used to vary the brightness of a light with radio control.
Technical specifications
Mains voltage:
Minimum power:
Maximum power:
Radio frequency band: 2400 - 2480 MHz
Maximum radio power
transmitted:
Ambient temperature:
Relative humidity:
Dimming:
Protections:
Dimensions:
Standard installation, 250W 1A power: when the module is installed in sealed flush-mount boxes which do not let air circulate,
the maximum permitted power is 250W, 1A current.
Specific installation, 500W 2A power: in some specific cases, if flush-mount boxes are connected by corrugated pipes which
let air through to provide ventilation or in open-air installation, the maximum permitted power is 500W, 2A current.
Dimmer wiring
with neutral
230V~ 50 Hz
Blue
wire
Load
Orange
wire
Red wire
DS1054-051C
230 V ~ (+10% -15%) - 50Hz
5 W
500 W 2 A, in normal installations
250 W 1 A, in installations in IP65
sealed boxes
10mW
from -20°C to +40°C
from 0 to 90%
on sinusoidal at start or end of phase
with automatic load type detection
short-circuit and overheating
protections
46 x 37 x 12 mm [1.81 x 1.46 x 0.47"]
Wiring
Installation on remote controlled sockets is risky because end users
could connect any type of electrical load and damage the module as
The flush mount version of the module is not equipped with terminal blocks.
It comes with wires, in conformity with the local safety regulation. To connect
the module to the circuit, appropriate terminals should be used according to
Optional
the specific National Safety Rules.
button
CAUTION
Accessory FDVDT (Code 5454075) must be installed if the power line of
the module is shared with inductive loads (e.g. window shutters or
ferromagnetic ballasts or ferromagnetic transformers). The accessory must
White
be connected as close as possible to the module in parallel between live and
wire
neutral. The internal overvoltage protection of the module could be rapidly
damaged without this accessory. The flush-mounted version of the module
is provided with wires but without terminal board. In-line terminals or similar
Aerial
connectors must be used to wire to the electrical network. The module must
be installed according to the rules in force in the country in which it is sold.
The module must be installed only by qualified personnel and
into a place the end-user cannot access, according to the
installing national rules.
In order to follow the safety rules, the module must be connec-
ted to a power line that is upstream protected by a magneto-
thermic switch 10A C curve.
With the low voltage light bulbs do not mix the ferromagnetic, elec-
tronic and toroidal transformers.
RADIO RANGE:
POWER range:
• inside 100 m² apartments with perpendicular crossing
of main wall or ceiling
• 250m in open range
(Note: in both cases the range may be reduced by pre-
sence of metallic elements, crossing of walls or parti-
tions).
RADIO TRANSMISSION
The transmitter LED will light up only if radio
transmission was successful.
Adding an intermediate receiver makes it possible to
solve a problem of insufficient range.
Refer to the transmitter instruction booklet for more infor-
mation.
DO NOT INSTALL ON REMOTE CONTROLLED SOCKETS
a consequence.
Installing Cautions
P9
GB