Cofem MiniCO MCO120 Manual página 23

Ocultar thumbs Ver también para MiniCO MCO120:
Idiomas disponibles

Idiomas disponibles

Table 2 shows the default values and the range of values between which they can be
configured: the delay time and the level of concentration of toxic gas for the activation of
ventilation 1 and the alarm for the MCO120 model.
Figure 1: Activation and deactivation of ventilation and alarm
Parameter
Ventilation level 1:
Ventilation 1 activation delay:
Ventilation 1 stop delay:
Alarm level:
Alarm activation delay:
Alarm stop delay:
Table 2: Parameters and values for the activation and deactivation of the alarm and ventilation.
Starting from rest, when the toxic gas concentration overcomes the ventilation level 1 in the
zone, this ventilation activates after having been above this level for a time greater than the
activation delay time 1.
If the toxic gas concentration in the zone drops below ventilation level 1, it will stop after the
stop delay time.
The Table 3 shows the default values and range of values that can be configured through the
front panel located on the control panel for the MCO120DVB model.
FABRICANTE DE PRODUCTOS CONTRA INCENDIOS– FIRE PROTECTION MANUFACTURER
C/ Compositor Wagner, 8 – P.I. Can Jardí - 08191 RUBÍ (Barcelona) ESPAÑA.
COsensor Control Panel
MCO120 / MCO120DVB
Value by default
50 ppm CO
4 min
4 min
200 ppm CO
1 min
1 min
FABRICANTE DE PRODUTOS CONTRA INCÊNDIOS
Tlf.: +34 935 862 690 - [email protected] -
Value Range
10 – 290 ppm CO
1 – 10 min
Fixed value
20 – 300 ppm CO
1 – 10 min
Fixed value
www.cofem.com
23
loading

Este manual también es adecuado para:

Minico mco120 dvb