System configuration
Ref.
Description of the funtionality
Pic. 6
1.0 It displays the revised firmware of the charge controller
Pressing and holding this button for 1 sec. all internal counters are reset to zero: NCicli
1
NOverTemp
, NOverVolt
2.0 Reset to zero fo energy counters
Pressing and holding this button for 1 sec. this energy counters are reset to zero. (E
3.0
It sets the charging voltage for battery.
The displayed voltage refers to the end-charge voltage at 25°C.
Pressing this button you can modify the setting.
Pressing and holding this button for 1 sec. you select the default value.
FLOOD program has to be set for the charge of flooded lead acid batteries.
3.1
SEAL program has to be set for either GEL or sealed batteries (default).
3.2
Li program must be used for the charge of Li-Ion batteries setting the end-charge voltage according to the instructions of
the manufacturer of the lithium battery.
The selectable values (in steps of 0.1 V) are:
3.3..3.10
14,0V; 14,1V; 14,2V; 14,3V; 14,4V; 14,5V; 14,6V; 14,7V; for 12V systems
28,0V; 28,2V; 28,4V; 28,6V; 28,8V; 29,0V; ,29,2V; 29,4V; for 24V systems
56,0V; 56,4V; 56,8V; 57,2V; 57,6V; 58,0V; 58,4V; 58,8V; for 48V systems
To choose the correct value of charging voltage for LiFePO4 batteries, is necessary to consult the manual of your
selected battery.
When the Li program is active, the end-charge voltage is not temperature compensated and it is set to the selected
value. The charging Float is excluded in Lithium configurations.
4.0
It sets the voltage threshold of intervention of Low-Battery protection (load disconnection in case of low battery).
Pressing this button is possible to modify the setting.
Pressing and holding this button for 1 sec. you select the default value
The selectable values are:
4.1..4.12
@12V: 10,80V; 10,96V; 11,12V; 11,28V; 11,44V; 11,60V; 11,76V; 11,92V; 12,08V; 12,24V; 12,40V; 12,56V;
@24V: 21,60V; 21,92V; 22,24V; 22,56V; 22,88V; 23,20V; 23,52V; 23,84V; 24,16V; 24,48V; 24,80V; 25,12V;
@48V: 43,20V; 43,84V; 44,48V; 45,12V; 45,76V; 46,40V; 47,04V; 47,68V; 48,32V; 48,96V; 49,60V; 50,24V;
5.0
It sets the threshold of the output voltage from Low-Battery protection (back to normal functionality).
Pressing this button is possible to modify the setting.
Pressing and holding this button for 1 sec. you select the default value
The selectable values are:
5.1..5.8
@12V: Aut(VEoC-0,20V); 12,72V; 12,88V; 13,04V; 13,20V; 13,36V; 13,52V; 13,68V;
@24V: Aut(VEoC-0,40V); 25,44V; 25,76V; 26,08V; 26,40V; 26,72V; 27,04V; 27,36V
@48V: Aut(VEoC-0,80V); 50,88V; 51,52V; 52,16V; 52,80V; 53,44V; 54,08V; 54,72V
6.0
It sets the mode of load operation.
Pressing this button is possible to modify the setting.
Pressing and holding this button for 1 sec. you select the default value
Load always ON during both day and night (24h/24h).
6.1
Load ON only during the night for the visualized hours (Twilight sensor with timer)
6.2..6.17
Load ON only during the night (complete twilight sensor)
6.18
WRM30+
User manual
1
1
, ContaOre
(except energy counters)
EN
1
1
, NLowBatt
, NOverLoad
, E
, E
, E
)
chA+EchB
chA
chB
LOAD)
1
,
10