RF SIGNAL PACK INSTALLATION INSTRUCTIONS
Acoustic Tile Mounting
Install the Threaded Insert, flange side, into the hole on the back of the sensor and turn
clockwise until it locks.
Keyhole Mounting
1. Use the template below to mark the location of mounting screws.
2. Install the provided screws – leaving approximately 3mm (1/8") space from the
bottom of the screw head to the ceiling (see Figures 2A and 2B).
3. Place the RF Signal Pack's mounting keyholes over screw heads and rotate sensor
clockwise until secured.
1
PLACE TEMPLATE on ceiling
2
Pierce and Mark both CENTER POINTS for Mounting Screws
1. Connect the CAT-5 cable coming out of the WRC-TX-LM to the
included LMRJ-S8 Splitter/Coupler.
2. Connect the LMRJ-S8 to an LMRJ cable and connect that cable to any
component in the DLM network. Connect to a Class 2 power source only.
Procedure for Binding
1. Press and hold BIND button on RF Signal Pack for 5
seconds until multi-colored LED on RF Signal Pack flashes
amber.
• All RF receptacles that are not already bound to an RF
Signal Pack will now flash green noting ready to bind.
• Any RF receptacle already bound to this RF Signal Pack
will flash amber.
• Any RF receptacle out of range or bound to another RF
Signal Pack will not change state.
• If your RF receptacle is not flashing, reset to factory
default state by holding the receptacle BIND button for
approximately 15 seconds until the LED is a solid amber.
2. Press and hold BIND button on RF Receptacle for 2
seconds until LED on receptacle flashes amber noting it is
properly bound.
If it was previously bound to this RF Signal Pack (was
flashing amber prior to holding BIND button for 2 seconds)
it will unbind and flash green.
3. Repeat for all RF receptacles in room network.
4. Return to original RF Signal Pack and press and hold BIND
button for 5 seconds until flashing LED on RF Signal Pack
turns off.
All RF receptacles on the same room network will stop
flashing indicating Binding is complete.
5. Test that binding has been successful by tapping the push button of the RF Signal Pack and confirm that the green led on the
receptacles turn on and off.
The green LED on the receptacle is on when the outlet has power, and off when the outlet is switched off. The bind button on the receptacle or
the RF Signal Pack can be pressed to override the occupancy sensor and turn on the receptacle temporarily.
Contains FCC ID: X7J-A11072401 and IC: 8975A-A11072401
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC
Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated
in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of
this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the
interference at his own expense.
CONNECTION TO A DLM SYSTEM
Daylight Sensor
OPERATING INSTRUCTIONS
2
7/8" (22mm) hole
Ceiling Tile
Screws: 70mm
(2.75") apart
Ceiling
Rotate clockwise
WARNING: TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE WIRING.
Ceiling Mount Sensor
DLM Local Network
LMRJ-S8
Switch
Wireless Connection
WRC-TX-LM
Figure 3: Connection Example
Nut
Washer
Threaded Insert
Figure 2A
Space: 3mm (1/8")
Figure 2B
Low Voltage
Line Voltage
LMRJ Cables
Room Controller
WRC-XX-x