GFCI Device Error
DCI Device Error
Current Sensor Error
AC Voltage Error
Frequency Error
No Grid Error
GFCI Error
DCI Error
ISO Error
Bus Voltage High
If this error occurs frequently, please contact your DNO or contact
Peimar assistance.
If this error occurs frequently, please contact your DNO or contact
Peimar assistance.
If this error occurs frequently, please contact your DNO or contact
Peimar assistance.
•
Check the volt of the grid.
•
Check the connection between the inverter and the grid.
•
Check the settings of the on-grid standards of the inverter.
•
If the voltage of the grid is higher than the standard value,
please conctact the Distribution Network Operator (DNO) for
the adjustment at the feed point or for the modification of the
regulated voltage value.
•
If the volt of the grid is in regulated range as allowed and
LCD still in this error, please contact your DNO or phone
Peimar.
Check the set of country and check the frequency of the local
grid, if the above mentioned are normal, please contact your DNO
or contact Peimar assistance.
Check the connection status between the AC side of the inverter
and the grid, if the above mentioned are in normal, please contact
your distributor or contact Peimar assistance.
Check the insulation resistance of the positive side and negative
side of the solar panel; check whether the inverter is in wet
environment; check the grounding of the inverter. If the above
mentioned are normal, please contact your DNO or contact
Peimar assistance.
If this error exists always, please contact your DNO or contact
Peimar assistance.
Check the insulation resistance of the positive side and negative
side of the solar panel; check whether the inverter is in wet
environment; check whether the grounding of the inverter is loose
or not. If the above mentioned are normal, please contact your
DNO or contact Peimar assistance.
Check the settings of the solar panel. Peimar designer can help
you. If the above mentioned are normal, please contact your DNO
or contact Peimar assistance.