Programming
Table 5 lists all available commands and parameters for the PENTEK INTELLIDRIVE.
Table 5 - Main Menu and Parameters
Menu
Parameter
Settings
Hour Format
Time
Time/Date
Date
Proportional
Gain
Integration
Time
PID Control
Derivation
Time
Derivative
Limit
Boost
Differential
Boost Delay
Sleep
Wake Up
Differential
Wake Delay
Password Time
Out
Password
Password
Unit of
Measure
Default
Hours
12Hr
HH:MM
1:00 AM
MM/DD/YYYY
1/1/12
–
1500
Milliseconds
1500 ms
Milliseconds
60 ms
–
120
PSI
3 PSI
MM:SS
1 Min
PSI
5 PSI
MM:SS
15 Sec
HH:MM
1 Hr
–
7777
Value
Min.
Max.
12Hr
24Hr
Selects 12 or 24 hour time scale.
Sets current time. Used for time
1
24
stamp in fault log.
Sets current date. Used for date
–
–
stamp in fault log.
Sets the PID controller gain. Used
in conjunction with all PID Control
0
10000
parameters to control how fast or
slow the Drive reacts to pressure
changes.
Sets the PID controller integration
time. Used in conjunction with all
65000
20 ms
PID Control parameters to control
ms
how fast or slow Drive reacts to
pressure changes.
Sets PID controller derivation time.
Used in conjunction with all PID
10000
0 ms
Control parameters to control how
ms
fast or slow Drive reacts to pressure
changes.
Sets derivative filter time constant
0
2000
for PID controller.
First part of Boost Process. Pressure
3 PSI
10 PSI
boost that happens before it goes to
Wake Delay.
The time Drive takes to start Boost
30 Sec
5 Min
Process after system has stabilized.
Pressure amount below setpoint that
5 PSI
15 PSI
wakes up Drive.
Second part of the Boost Process.
3 Sec
2 Min
The time it takes to ramp down
pressure during the Boost Process.
Amount of time it takes to lock
1 Min
6 Hr
keypad (after last button is pressed).
0000
9999
Password used to unlock keypad.
13
Description