loss. If the room is now unoccupied, the load will turn OFF once vacancy is detected.
• Default To Off – The load stays off after power is restored.
Presentation Mode / Disable Presentation Mode
Presentation Mode is a feature of the Auto ON mode. When the relay is manually turned OFF, the PW holds the lights OFF until no
motion has been detected for the duration of the Time Delay. With subsequent occupancy, the PW turns the load ON. By default,
Presentation Mode is enabled.
When Presentation Mode is disabled and the relay is manually turned OFF, the sensor will not retrigger load ON until the room is
determined to be vacant for a 15 second period. Following that 15 second time delay, the load will retrigger with Auto-On functionality.
This feature is intended for use in transient spaces or rooms such as bathrooms, where you always want the loads to turn ON as soon as
occupancy is detected.
Service Mode
In Service Mode, the occupancy sensor and light level functions are temporarily disabled. The button will still turn the load ON and OFF.
Preset On Level
If Auto On is selected, the value of this feature determines the dimming level that the load will go to when turned ON by occupancy
detection. Available values are the most recent (non-zero) amount (the default), 50%, 75%, or 100%.
Non-Dim Mode
This feature changes the buttons so that they function as simple on/off switches, with no dimming. The UP button turns the load ON and
the Down button turns it OFF. This feature is turned off by default.
Reset to Factory Default
Press and hold the Up or Down button for 5 seconds. The green LED will flash 3 times to indicate the reset is complete. Return the DIP
Switches 6-9 to the OFF state. This resets the sensor and disables light level control (the brightest ambient light will not hold the light
OFF).
DIP SWITCH SETTINGS
Time
Delay
ON
1
2
Mode
Manual - On
Auto - On
Time Delay
Test/3 min
5 minutes
15 minutes
30 minutes
=ON
Default Values Shown
in Bold
COVERAGE PATTERNS
Coverage testing has been performed according to the NEMA WD 7 guideline. For best performance, use in spaces not larger than 15' x 12'.
PIR Sensor
The sensor has a two-tiered, multi-cell viewing Fresnel lens with 180 degree field of view. The red LED on the sensor flashes when the
PIR detects motion.
Masking the lens
Opaque adhesive tape is supplied so that sections of the PIR sensor's view can be masked. This allows you to eliminate coverage
in unwanted areas. Since masking removes bands of coverage, remember to take this into account when troubleshooting coverage
problems.
Additional
Additional Features
Features
Exit Programming Mode
3
4
5
6
7
8
9
Unused
1
Mode
Light Level Adjust
2 3
Power Loss Mode
Presentation Mode
=OFF
Call 800-879-8585 for Technical Support
6 7
8 9
Visual Alert
Audio Alert
Walk-Thru
PIR Sensitivity
High Trim
Low Trim
Ramp Up Time
Fade Down Time
Service Mode
Preset On Level
Non-Dim Mode
Reset To Default
Green LED # of Blinks
1=OFF, 2=ON
1=ON, 2=OFF
1=OFF, 2=ON
1=100%, 2=50%
1=10V, 2=Manual Adjustment
1=0V, 2=Manual Adjustment
1=1, 2=2.5, 3=5, 4=10 seconds
1=2.5, 2=5, 3=15, 4=30 seconds
1=Disable, 2=Enable,
3=Smart Light Level
1=Keep Last State,
2=Default On, 3=Default Off
1=ON, 2=OFF
1=OFF, 2=ON
1=Last Non-Zero Value,
2=50%, 3=75%, 4=100%
1=OFF, 2=ON
Press and Hold UP or
DOWN for 5 seconds