Allen-Bradley Bulletin 855XH Horn Manual De Instrucciones página 2

Bulletin 855XH Horn
RATING AND MARKING INFORMATION
NEC & CEC Class / Division Ratings for US / Canada
855XH-BN***B horns comply with the following standards:
UL 121201-2021 (Ed. 9)
CAN/CSA C22.2 No. 213-17 (Ed. 3)
855XH-BN***B horns are rated as follows:
Class I, Div 2,
ABCD
Class I, Div 2,
ABCD
Class II, Div 2,
FG
Class III ,Div 1 & 2
Installation must be carried out in compliance with the National Electric Code / Canadian Electric Code
NEC Class / Zone ratings US
855XH-BN***B horns comply with the following standards:
UL 60079-0 (Ed. 7): Explosive Atmospheres - Part 0: Equipment - General Requirements
UL 60079-7 (Ed. 5): Explosive Atmospheres - Equipment Protection by Increased Safety "e"
UL 60079-31 (Ed. 2): Explosive Atmospheres - Equipment Dust Ignition Protection by Enclosure "t"
855XH-BN***B horns are rated as follows:
Class I Zone 2 AEx ec IIC T4 Gc Ta -20°C to +55°C
Zone 22 AEx tc IIIC T85°C Dc Ta -20°C to +55°C
Installation must be carried out in compliance with the National Electric Code.
CEC Class / Zone ratings Canada
855XH-BN***B horns comply with the following standards:
CAN/CSA C22.2 No. 60079-0 (Ed. 4) 02/2019: Explosive Atmospheres - Part 0: Equipment - General Requirements
CAN/CSA C22.2 No. 60079-7 (Ed. 2): Explosive Atmospheres - Equipment Protection by Increased Safety "e"
CAN/CSA C22.2 No. 60079-31 (Ed. 2): Explosive Atmospheres - Equipment Dust Ignition Protection by Enclosure "t"
855XH-BN***B horns are rated as follows:
Ex ec IIC T4 Gc Ta -20°C to +55°C
Ex tc IIIC T85°C Dc Ta -20°C to +55°C
Installation must be carried out in compliance with the Canadian Electric Code
ATEX / IECEx / UKEx Certifications
855XH-BN***B horns comply with the following standards:
EN IEC 60079-0:2018 / IEC60079-0:2017 (Ed 7): Explosive Atmospheres - Equipment. General Requirements
EN IEC 60079-7:2015 +A1:2018 / IEC 60079-7:2018 (Ed. 5.1): Explosive Atmospheres - Equipment Protection by Increased Safety "e"
EN 60079-31:2014 / IEC 60079-31:2013 (Ed 2): Explosive Atmospheres - Equipment Dust Ignition Protection by Enclosure "t"
855XH-BN***B horns are rated as follows:
II 3G Ex ec IIC T4 Gc Ta -20°C to +55°C
II 3D Ex tc IIIC T85°C Dc Ta -20°C to +55°C
Zones, Gas / Dust Groups and Temperature Classification
When connected to an approved system the 855XH may be installed in:
Zone 2 explosive gas air mixture not likely to occur in normal operation, and if it does, it will only exist for a short time.
Zone 22 explosive dust air mixture not likely to occur in normal operation, and if it does, it will only exist for a short time.
May be used with gases in groups:
Group IIA
propane
Group IIB
ethylene
Group IIC
hydrogen / acetylene
May be used with Dust types:
Group IIIA
combustible flyings
Group IIIB
non-conductive dust
Group IIIC
conductive dust
Installation must be carried out in compliance with the latest issue of the following standards:
EN60079-14 / IEC60079-14: Explosive atmospheres - Electrical installations design, selection and erection
EN60079-10-1 / IEC60079-10-1: Explosive atmospheres - Classification of areas. Explosive gas atmospheres
EN60079-10-2 / IEC60079-10-2: Explosive atmospheres - Classification of areas. Explosive dust atmospheres
Publication 855X-IN002C-EN-E-January 2023
T3C Ta -20°C to +55°C
T4 Ta -20°C to +40°C
T6 Ta -20°C to +55°C
Ta -20°C to +55°C
Having a temperature classification (for Gas applications) of:
T1
450ºC
T2
300ºC
T3
200ºC
T4
135ºC
Maximum Surface Temperature for Dust Applications:
85ºC
Certificate No.
IECEx UL 19.0059X
DEMKO 19 ATEX 2233X
UL22UKEX2682X
CE Marking
UKCA Marking
DIR 10004893329 (Version 02)
2
loading

Este manual también es adecuado para:

855xh-bnd30b855xh-bna10b855xh-bna20b