3.2.2 Superheating and sub cooling submode (SH SC)
Press the
key to enter the subcooling of superheating and subcooling, The interface[
MODE
FIG.2 ]displays the measured pressure, temperature, superheat and subcooling values at
the high and low pressure sides.
Superheating
3.2.3 Temperature difference submode (∆T)
Press the
MODE
displays the measured pressure,temperature and temperature difference values at the high
and low pressure sides.
3.3 Vacuum Measurement Mode(VAC)
1.Connect the refrigerant hose on the high-pressure side to the tested system and open the
high-pressure valve.
The high-pressure side channel is the vacuum test of the system.
2.Press the
+
MODE
interface.
3.The product connects the vacuum pump and the tested system.
4.Start the vacuum pump to extract the pressure in the system.
!
When the pressure in the system is lower than atmospheric pressure (i.e. the pressure display is less than
0)the system vacuum degree is displayed,otherwise, - - - - is displayed.
5.The interface [ FIG.4] displays the current pressure value of the system, the vacuum degree
of the system and the timing of entering the interface .
FIG.2 Diagram of Superheat and Subcooling Submode
key to enter the temperature difference submode,the interface [ FIG.3 ]
FIG.3 Diagram of Temperature Difference Submode
combination keys briefly in PT mode to enter the vacuum test VAC
6
Subcooling