Condensate Pan Draining Connection - CIAT COADIS LINE 900 Manual De Instrucciones

Ocultar thumbs Ver también para COADIS LINE 900:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 50
- Cooling coil inlet minimum water temperature: 6°C
- Heating coil inlet maximum water temperature (2-tube application without electrical
heaters): 70°C
- Heating coil inlet maximum water temperature (2-tube application without electrical
heaters): 55°C (min. air flow rate = 200 m
- Heating coil inlet maximum water temperature (4-tube application): 80°C
- Maximum operating pressure: 16 Bar
- Interior return air min./max. temperature: +0°C / +40°C
- Indoor return air maximum humidity level:
Humidity).
To prevent any inopportune opening of the thermo-actuators on control valves with
thermal motors, the temperature of the air surrounding the thermo-actuators should
not exceed 50°C. This is especially important for units installed in confined spaces
(e.g. in suspended ceilings).
To protect against the risk of condensation when using chilled water, lagging should
be placed along the entire lengths of pipes and completely sealed at its ends.
When using the water coil and electric heater, we advise against using cross-linked
the electric heater could cause the water temperature to rise briefly. This could cause
We recommend using stainless steel braided (or equivalent) hoses for hydraulic
connections.

4.4. Condensate pan draining connection

A naturally inclined ABS auxiliary condensate drain pan, with no water retention, is
supplied with the unit.
To install this auxiliary pan, proceed as follows:
- Remove the bolt (Fig. 17, a)
- Clip on the auxiliary pan
- Refit the bolt and tighten it (Fig. 17, b).
The condensate is drained via the drain hole in the pan (drain height 70 mm); This
drainage bushing is the lowest point on the auxiliary pan so that water does not
accumulate in the pan. The drain pipe can be separate for each unit or connected to
a main drain pipe sized to allow the condensates from all the units to flow through
at the same time. Use a clear flexible and/or rigid drain pipe for a minimum slope of
1 cm/m, with a constant gradient along its whole length and no low points. Install a
trap measuring at least 5 cm to prevent unpleasant gases or odours exiting the hose.
N 12.59C
3
/h)
(Dry Bulb) at 65% RH (Relative
65°C