Setting the kind of sensor to be connected to the device:
push the Enter button: on the lower display (green) Opr appears. Using the up and down arrows find ConF. Push
Enter to confirm.
Now on the green display the group InP appears. Push Enter and InP1 is displaied. Enter to confirm.
You are inside InP1; the green display shows Sen1 (sensor type), while the red display shows the chosen sensor
code
Push Enter to enter the Sen1 parameter, then choose the desired sensor using the arrows. Push Enter to confirm
and ESC to escape.
Once selected the sensor, you can modify all the other parameters using up and down arrows according to the
tables here below.
ConF > InP >InP1
Parameter
SEn1
type
of
sensor
for
analog input 1
OFF1
sensor offset
SCL1
scale low level
SCH1
scale high level
dF1
digital filter
Unit
temperature unit
(bold = factory settings)
Remark:
RWF50.2 e RWF50.3 cannot be connected to thermocouples.
If thermocouples have to be connected, convert the signal to a 4-20 mA one and set the RWF accordingly.
Value
1
2
3
4
5
6
7
15
16
17
18
19
-1999..0.. +9999
-1999..0.. +9999
-1999..100.. +9999
0...0,6...100
1
2
Description
Pt100 3 fili
Pt100 2 fili
Pt1000 3 fili
Pt1000 2 fili
Ni1000 3 fili
Ni1000 2 fili
0 ÷ 135 ohm
0 ÷ 20mA
4 ÷ 20mA
0 ÷ 10V
0 ÷ 5V
1 ÷ 5V
Using the measured value correction (offset), a measured
value can be corrected to a certain degree, either up or down
In the case of a measuring transducer with standard signal, the
physical signal is assigned a display value here
(for input ohm, mA, V)
In the case of a measuring transducer with standard signal, the
physical signal is assigned a display value here
(for input ohm, mA, V)
Is used to adapt the digital 2nd order input filter
(time in s; 0 s = filter off)
1 = degrees Celsius
2 = degrees Fahrenheit