AKO -80013 Guía De Instalación Rápida página 2

GB
AKO-80013 HUMIDITY PROBE
1- Description
Surface-mounted humidity probe with 4-20 mA output
2- Installation
Fix the probe using at least two screws (A), wire it by passing the cable through the
gland (B) supplied and close the cover using the 4 screws provided (C).
3- Warnings
Ensure that the operating conditions are not exceeded in the place of
installation (see technical features).
Do not install it close to sources of heat, excessive dust, mechanical vi-
bration or where it might be exposed to direct sunlight or magnetic
fields.
Submitting it to sudden temperature changes may produce internal conden-
sation. In this case, wait for about one hour before switching on the power.
Ensure that the supply voltage is within the admissible range (see tech-
nical features).
Disconnect the power supply beforing performing any type of maintenance.
4- Wiring
Without external supply
AKO-15740/15742
1
2
INPUT NO.
1 2 3 4
RH
V+
AKO-80013
V+
RH
AKO-80013
With external supply
AKO-15750/15752
INPUT NO.
1
1 2 3 4 5
+
80014A
RH
V+
AKO-80013
5- Technical specifications
Protection:.......................................................IP65
Power supply:..................20 to 35 VDC (RL<500W)
.........................................11 to 35 VDC (RL<50W)
Sensor type:......................................................ESD
INPUT NO.
1 2 3 4 5
RH
AKO-80013
AKO-14532/14534
ENTRADA
1 2 3
L
AKO
230Vca
N
RH
AKO-80013
AKO-15750/15752
1
V+
RH
V+
AKO-80013
4
L
AKO
230Vca
+
80014A
N
V+
Ambient working temperature: ...................-5 to 50 ºC
Ambient storage temperature: ..................-25 to 60 ºC
Calibration:.........0/100% RH (0=4 mA y 100=20 mA)
Measurement range: .............................10 to 95% RH
2
A
M16
(Cable ø 4,5 - 10 mm)
B
5 0
± 0
, 3
V+: +V
Rh: Output
AKO-14532/14534
AKO-D1472x / D1472x-C
ENTRADA
1 2 3
4
V+ RH
AKO-80013
AKO-D1472x / D1472x-C
ENTRADA
1 2 3 4 5
AKO
+
80014A
RH
V+
AKO-80013
C
A
L
230Vca
N