2.

Warranty

Liability is accepted in accordance with the General Terms and Conditions of
Business and Supply.
Use original spare parts only!
3.

Important notes

• Assembly, commissioning and maintenance may only be carried out by a qualified
technician in accordance with the instructions.
• The statutory regulations and conditions for technical connection to the local
water supply companies must be adhered to.
• Prior to the assembly process, flush the pipework in accordance with DIN 1988.
• Mount the eye shower in accordance with EN 15154 Part 2.
• Replace the filter once a year.
• We reserve the right to make changes.
4.

Application

Emergency showers are prescribed first aid installations for work stations where
hazardous materials are being handled.
Eye and facial shower with water collection basin for wall mounting, including
bracket for hand shower.
5.

Technical specifications

Water connection:
Minimum flow pressure:
Flow pressure range:
Volumetric flow:
6.

Scope of delivery

7.

Dimensions

8.

Installation example

4
G 3/8 B
1.0 bar
1-4 bar
This range meets the requirements of
EN 15154.
Constant 6-9 l/s at a flow pressure of 1 bar