B - distance >1.5 m
C - distance <1.5 m
D - 0.5 m above the highest point of the roof
E - 0.8 m
F - drainage area
Roof with a slope of 45
•
A - min. 2 m
B - distance >1.3 m
C - distance <1.3 m
D - 0.5 m above the highest point of the roof
E - 2.1 m
F - drainage area
Requirements for the end of the chimney:
Do not route the chimney to end in closed or roofed spaces (e.g. carport,
•
garage, attic, mezzanine, under the sun deck, porch, staircase, vestibule,
etc.)
•
The surface of the exhaust pipe can reach really high temperatures (up to
160
C), so it should have a resistant to high temperatures, non-flammable
°
warning against the risk of severe burns or properly insulated with non-
flammable material.
The end of the ventilation chimney must be higher than the air inlet pipe.
•
If the smoke is discharged directly through the wall, it is recommended that
the vertical chimney pipe be at least 1.5 m long for outdoor installation.
This will prevent the ingress of smoke and its odor back into the building
degrees