5 Installation
5.7.3
Connecting the units
Fig.130
5.8
Completing the installation
5.8.1
Protecting the refrigerant pipes with tape
Fig.131
5.8.2
Checking the condensate drain
132
Caution
Use a suitable cable: power supply cables of parts of appliances
for outdoor use shall not be lighter than polychloroprene sheathed
flexible cable (design 60245 IEC 57).
230V~
50Hz
L
L
N N N
1. Connect the cables to the appropriate terminals, as shown in the
figure.
Important
To avoid electric shock, make sure that the length of the
conductors between the traction arrester device and the terminal
blocks is such that the active conductors are put under tension
before the earth conductor.
Important
Correctly screw the cable clamps. Adjust the length of the cables
accordingly.
1. Wrap the refrigerant pipes, the power and communication cables from
bottom to top with tape.
2. Use clamps or other suitable accessories to secure the refrigerant
pipes to the wall.
3. Use expanding foam to fill the opening in the wall around the
refrigerant pipes.
MW-6020025-01
Geographic location and weather can influence the time for condensates
to appear. Follow instructions for the indoor unit and outdoor unit.
1. Start the air conditioner.
2. Pour water directly into the condensate pan.
3. Check that the water is drained off smoothly and correctly.
MW-6020124-1