DUCTING TO HVAC SYSTEMS (Closet Installations)
CAUTION!
PLEASE NOTE: RETURN TO RETURN INSTALLS ARE TO BE CONSIDERED LAST RESORT OPTIONS AND ARE
NOT RECOMMENDED. THE DEHUMIDIFIER WILL HEAT THE AC COOLING COILS WHICH DIMINISHES THE
AMOUNT OF WATER THE AC SYSTEM WILL REMOVE WHEN OPERATING. PLEASE CHECK YOUR LOCAL
CODES PRIOR TO INSTALLING.
2. Alternative Closet Installation
If the Recommended Closet Installation is not possible, there are alternative installation options available.
No inlet duct is required. Air is pulled through the louvers or grille from the living space.
Control should be placed in a central location or the onboard control can be used for this installation.
a. Central Return to HVAC Return
Duct the supply of the Ultra Series
Dehumidifier to the return side of the
existing HVAC system.
In a central return system, the HVAC
fan must run when the dehumidifier is
running.
b. No Duct - Central Return to HVAC Return
Attach outlet duct with a vertical flow
through so air is not discharged into
wall or other obstruction. The HVAC
system will naturally pull dehumidified
air from the closet and distribute it
throughout the structure.
16
Santa Fe ULTRA70 Installation & Operation Instructions
HVAC
Return
Ultra Series
Return
HVAC
Return
Ultra Series
Return
HVAC
Supply
Backdraft
Ultra Series
Damper
Supply
HVAC
Supply
Ultra Series
Supply