Installation Instructions
IL Area Controller with
SCMA0401 Adaptive Dimmer
IMPORTANT: Read carefully before installing product. Retain for future reference.
Failure to comply with these instructions may result in serious injury (including death)
and property damage.
Risk of Fire, Electrical Shock, Cuts or other Casualty Hazards- Installation and maintenance of this product must be
performed by a qualified electrician. This product must be installed in accordance with the applicable installation code
by a person familiar with the construction and operation of the product and hazards involved. For continued protection
against shock hazard replace all covers and guards after field wiring is completed.
Before installing or performing any service, the power MUST be turned OFF at the branch circuit breaker. According to NEC
240-83(d), if the branch is used as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked
with "SWD". All installations should be in compliance with the National Electric Code and all state and local codes.
Risk of Fire and Electric Shock- Make certain power is OFF before starting installation or attempting any maintenance.
Disconnect power at fuse or circuit breaker. WaveLinx Wired models may contain circuits from more than one power
source.
Risk of Burn- Disconnect power and allow product to cool before handling or servicing.
Risk of Personal Injury- Due to sharp edges, handle with care. Always use at least two people when lifting and mounting
heavy or large units
DISCLAIMER OF LIABILITY: Cooper Lighting Solutions assumes no liability for damages or losses of any kind that may arise from the
improper, careless, or negligent installation, handling or use of this product.
NOTICE: Product may become damaged and/or unstable if not installed properly.
Note: Specifications and dimensions subject to change without notice.
ATTENTION Receiving Department: Note actual product description of any shortage or noticeable damage on delivery receipt.
File claim for common carrier (LTL) directly with carrier. Claims for concealed damage must be filed within 15 days of delivery. All
damaged material, complete with original packing must be retained.
NOTICE: If a room is wired for two circuits using two separate hot leads, it is very important to connect only one circuit per relay.
Both circuits must be fed from the same phase.
NOTICE: Ensure that all modules are firmly seated on the DIN rails before beginning field wiring.
NOTICE: The high voltage supply should be fed to the cabinet via an external isolation breaker with sufficient capacity for the planned
installation.
NOTICE: Ensure that the supply is fully isolated at an external breaker before opening doors. Test that power has been removed before
starting to handle conductors.
NOTICE: Ensure that high voltage and low voltage wiring remains separate.
NOTICE: All new wiring must be fully verified before applying power.
NOTICE: Designed for indoor installation and use only. Dry location rated.
WARNING
WaveLinx Wired
Applies to Model #s:
ILS-SCMA0401-1
ILM-SCMA0401-2
ILM-SCMA0401-3
Tabla de contenido
loading

Resumen de contenidos para Cooper Lighting Solutions SCMA0401

  • Página 1 Risk of Personal Injury- Due to sharp edges, handle with care. Always use at least two people when lifting and mounting heavy or large units DISCLAIMER OF LIABILITY: Cooper Lighting Solutions assumes no liability for damages or losses of any kind that may arise from the improper, careless, or negligent installation, handling or use of this product.
  • Página 2: General Information

    WaveLinx Wired IL Area Controller with SCMA0401 Adaptive Dimmer Please read before installing General information The WaveLinx Wired panels are designed, built and tested to strict safety regulations. By following the steps listed below and Cabinet Dimensions elsewhere within this guide, you can ensure safe installation and ILS-*: Small Enclosure (two DIN rail modules) operation of these controller units.
  • Página 3 WaveLinx Wired IL Area Controller with SCMA0401 Adaptive Dimmer Mounting the enclosure To mount the enclosure The WaveLinx Wired modules consist of an enclosure with Choose a dry location convenient to the circuit breaker interior DIN rail modules. Interior DIN rail modules include: panel that meets the operating temperature requirements.
  • Página 4: Wiring Information

    SCMA modules also enter from the top of the cabinet. Ground connections are provided at the top of the cabinet for landing The AC dimmer modules (SCMA0401-NA) will be pre-mounted grounding conductors. on interior DIN rail per the order specifications.
  • Página 5 WaveLinx Wired IL Area Controller with SCMA0401 Adaptive Dimmer Single channel AC Dual channel AC Line Line Line Neutral Neutral Single channel load Dual channel load Mains Power Loads Mains Power Loads www.cooperlighting.com IB50301922 page 5 May 2022...
  • Página 6 WaveLinx Wired panels. The lighting network is a daisy-chain and requires one in and one out connection. The lighting network also requires a terminating jumper installed at the two ends of the network Lighting network wire should use Cooper Lighting Solutions LCCP or LCCNP wire (alternate: Belden 1502, 1502P). Lighting network wiring detail...
  • Página 7 WaveLinx Wired IL Area Controller with SCMA0401 Adaptive Dimmer Typical connection diagram Incoming Supply 120 - 277V AC Mains supply protection: Provided by installer (6A Type C MCB recommended) Lamps Manual Control Buttons Device Identification Button IMPORTANT NOTE: Connecting a mains potential cable to the iCAN Network terminals is likley to damage the unit and other devices connected, and invalidate warranty.
  • Página 8: Important

    Risque de blessures – À cause des arêtes tranchantes, manipulez ce produit avec précaution. EXONÉRATION DE RESPONSABILITÉ : Cooper Lighting Solutions n’assume aucune responsabilité pour les dommages ou pertes de quelque nature que ce soit pouvant découler d’une installation, d’une manipulation ou d’une utilisation inappropriée, imprudente ou négligente de ce produit.
  • Página 9: Renseignements Généraux

    Retirez le matériel de l’emballage et mettez-le au rebut avant de procéder au câblage sur le terrain. Cela comprend les séparateurs en carton dans les petites armoires et les attaches en plastique utilisées sur tous les modules SCMA0401. 25-11/32” 25-1/8”...
  • Página 10 WaveLinx Wired Contrôleur de zone IL avec gradateur adaptatif SCMA0401 Montage de l’enceinte Pour monter l’enceinte Les modules WaveLinx Wired comportent une enceinte dotée Choisissez un endroit sec et pratique qui répond aux de modules de rail DIN à l’intérieur. Les modules de rail DIN exigences relatives à...
  • Página 11: Raccordement De L'alimentation

    120 à 277 V. débris de câbles de l’enceinte. 4 canaux de gradation sont prévus sur chaque module SCMA0401-NA. Les canaux 1+2 et 3+4 peuvent être combinés Classe 2 Entrée à basse tension pour permettre un contrôle plus important de la charge.
  • Página 12 WaveLinx Wired Contrôleur de zone IL avec gradateur adaptatif SCMA0401 CA à un canal CA à deux canaux Ligne Ligne Ligne Neutre Neutre Charge à un canal Charge à deux canaux Charges de l’alimentation secteur Charges de l’alimentation secteur IB50301922 page 12 www.cooperlighting.com...
  • Página 13 Ce réseau exige également l’installation d’une bretelle de terminaison installée aux deux extrémités. Le câble du réseau d’éclairage doit utiliser le câble LCCP ou LCCNP de Cooper Lighting Solutions (alternative : Belden 1502, 1502P). Détails sur le câblage du réseau d’éclairage Renseignements sur le câblage :...
  • Página 14: Diagramme De Connexion Typique

    WaveLinx Wired Contrôleur de zone IL avec gradateur adaptatif SCMA0401 Diagramme de connexion typique Alimentation entrante 120-277 V CA Protection de l’alimentation secteur : Fourni par l’installateur (MCB type C 6 A recommandé) Lampes à Boutons de contrôle manuel Identification du dispositif Bouton REMARQUE IMPORTANTE : Le raccordement d’un câble du...
  • Página 15: Controlador De Área Il Con Atenuador Adaptable Scma0401

    Risque de blessures – À cause des arêtes tranchantes, manipulez ce produit avec précaution. RENUNCIA DE RESPONSABILIDAD: Cooper Lighting Solutions no asume ninguna responsabilidad por daños o pérdidas de ningún tipo que puedan surgir por la instalación, manipulación o uso inadecuado, descuidado o negligente de este producto.
  • Página 16: Leer Antes De La Instalación

    • Los recintos están diseñados para montaje en superficie. Consulte a Conecte el cableado del circuito derivado. Cooper Lighting Solutions antes de intentar el montaje al ras. Conecte el cableado del bus de datos de 2 hilos. • Utilice los conductos y los acopladores adecuados para conectar las Conecte el cableado de la red WaveLinx Wired.
  • Página 17: Montaje Del Recinto

    WaveLinx Wired Controlador de área IL con atenuador adaptativo SCMA0401 Montaje del recinto Para montar el recinto Los módulos WaveLinx Wired consisten en un recinto con Elija una ubicación seca que sea conveniente para el panel módulos interiores de riel DIN. Los módulos interiores de riel...
  • Página 18: Flujo Del Cableado

    Conexión de cargas de atenuadores de 120 V-277 V CA. tierra. Los módulos de atenuación de CA (SCMA0401-NA) se montan Nota: Compruebe el voltaje nominal indicado en el controlador previamente en el riel DIN interior según las especificaciones antes de conectarlo a la red eléctrica y verifique que coincida...
  • Página 19 WaveLinx Wired Controlador de área IL con atenuador adaptativo SCMA0401 Canal único de CA Doble canal de CA Línea Linea Linea Neutro Neutro Carga de canal único Carga de doble canal Cargas de la alimentación principal Cargas de la alimentación principal www.cooperlighting.com...
  • Página 20: Detalle Del Cableado De La Red De Iluminación

    La red de iluminación también requiere un puente de terminación instalado en los dos extremos de la red. El cable de la red de iluminación debe utilizar el cable LCCP o LCCNP de Cooper Lighting Solutions (alternativo: Belden 1502, 1502P).
  • Página 21: Diagrama De Conexión Típico

    WaveLinx Wired Controlador de área IL con atenuador adaptativo SCMA0401 Diagrama de conexión típico Suministro de entrada 120 - 277 V CA Protección de la alimentación principal: Proporcionado por el instalador (se recomienda un MCB de tipo C de 6 A) Lámparas...