Installation Instructions
IL Area Controller with
SCMA0401 Adaptive Dimmer
IMPORTANT: Read carefully before installing product. Retain for future reference.
Failure to comply with these instructions may result in serious injury (including death)
and property damage.
Risk of Fire, Electrical Shock, Cuts or other Casualty Hazards- Installation and maintenance of this product must be
performed by a qualified electrician. This product must be installed in accordance with the applicable installation code
by a person familiar with the construction and operation of the product and hazards involved. For continued protection
against shock hazard replace all covers and guards after field wiring is completed.
Before installing or performing any service, the power MUST be turned OFF at the branch circuit breaker. According to NEC
240-83(d), if the branch is used as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked
with "SWD". All installations should be in compliance with the National Electric Code and all state and local codes.
Risk of Fire and Electric Shock- Make certain power is OFF before starting installation or attempting any maintenance.
Disconnect power at fuse or circuit breaker. WaveLinx Wired models may contain circuits from more than one power
source.
Risk of Burn- Disconnect power and allow product to cool before handling or servicing.
Risk of Personal Injury- Due to sharp edges, handle with care. Always use at least two people when lifting and mounting
heavy or large units
DISCLAIMER OF LIABILITY: Cooper Lighting Solutions assumes no liability for damages or losses of any kind that may arise from the
improper, careless, or negligent installation, handling or use of this product.
NOTICE: Product may become damaged and/or unstable if not installed properly.
Note: Specifications and dimensions subject to change without notice.
ATTENTION Receiving Department: Note actual product description of any shortage or noticeable damage on delivery receipt.
File claim for common carrier (LTL) directly with carrier. Claims for concealed damage must be filed within 15 days of delivery. All
damaged material, complete with original packing must be retained.
NOTICE: If a room is wired for two circuits using two separate hot leads, it is very important to connect only one circuit per relay.
Both circuits must be fed from the same phase.
NOTICE: Ensure that all modules are firmly seated on the DIN rails before beginning field wiring.
NOTICE: The high voltage supply should be fed to the cabinet via an external isolation breaker with sufficient capacity for the planned
installation.
NOTICE: Ensure that the supply is fully isolated at an external breaker before opening doors. Test that power has been removed before
starting to handle conductors.
NOTICE: Ensure that high voltage and low voltage wiring remains separate.
NOTICE: All new wiring must be fully verified before applying power.
NOTICE: Designed for indoor installation and use only. Dry location rated.
WARNING
WaveLinx Wired
Applies to Model #s:
ILS-SCMA0401-1
ILM-SCMA0401-2
ILM-SCMA0401-3