Addressing
Each siren requires a numeric address between 128 and 252
for identification purposes. This is set using DIP switches 1-7
located at the rear of the unit (see page 16).
Maintenance
Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry.
Technical specifications
Operating voltage
Loop current consumption
(quiescent)
Loop current consumption (alarm)
Sound pressure level (SPL)
Frequency (intermittent 500 ms
ON / 500 ms OFF)
Maximum number of sirens per
loop
IP rating
Operating temperature
Storage temperature
Relative humidity
Dimensions
* SPL values can vary depending on the angle and distance of the user
from the siren. The following table indicates SPL values at a distance
of 1 metre on the horizontal plane using an operating voltage of 36 V.
Angle
15°
45°
75°
105°
135°
165°
Regulatory information
This section provides a summary on the declared performance
according to the Construction Products Regulation
(EU) 305/2011 and Delegated Regulations (EU) 157/2014 and
(EU) 574/2014.
For detailed information, see the product Declaration of
Performance (available at firesecurityproducts.com).
Certification
Certification body
Declaration of
Performance number
Year of first CE marking
Product identification
Intended use
Declared performance
2 / 16
21 to 36 V
300 µA
max. 6 mA
76 to 86 dB(A)*
800 hz
20
IP21C
–20 to +50ºC
–20 to +70ºC
max. 95%
63 x Ø 93 mm
SPL value (min.)
76 dB(A)
82 dB(A)
86 dB(A)
86 dB(A)
82 dB(A)
76 dB(A)
0370
360-4109-0199
07
SK08A
See the product Declaration of
Performance
See the product Declaration of
Performance
Manufacturer
Contact information and product
documentation
For contact information or to download the latest product
documentation, visit firesecurityproducts.com.
Product warnings and disclaimers
THESE PRODUCTS ARE INTENDED FOR SALE TO AND
INSTALLATION BY QUALIFIED PROFESSIONALS.
CARRIER FIRE & SECURITY B.V. CANNOT PROVIDE ANY
ASSURANCE THAT ANY PERSON OR ENTITY BUYING ITS
PRODUCTS, INCLUDING ANY "AUTHORIZED DEALER" OR
"AUTHORIZED RESELLER", IS PROPERLY TRAINED OR
EXPERIENCED TO CORRECTLY INSTALL FIRE AND
SECURITY RELATED PRODUCTS.
For more information on warranty disclaimers
and product safety information, please check
https://firesecurityproducts.com/policy/product-
warning/ or scan the QR code:
P/N 10-4221-501-3SKO-05 • ISS 04OCT21
Carrier Safety System (Hebei) Co. Ltd.,
80 Changjiang East Road, QETDZ,
Qinhuangdao 066004, Hebei, China.
Authorized EU manufacturing
representative:
Carrier Fire & Security B.V.,
Kelvinstraat 7, 6003 DH Weert,
Netherlands.
2012/19/EU (WEEE directive): Products
marked with this symbol cannot be
disposed of as unsorted municipal waste
in the European Union. For proper
recycling, return this product to your local
supplier upon the purchase of equivalent
new equipment, or dispose of it at
designated collection points. For more