PV array to earth insulation resistance adjustable
range
Sudden change residual current limits and res-
ponse times
Continuous current limits and response times
Continuous current limits adjustable range
PV array insulation test timer
PV array insulation test timer adjustable range
Output data
Grid voltage range
Rated grid voltage
Rated power
Rated apparent power
Rated frequency
Power factor cos phi
Grid connection
Maximum output power
Rated power
Nominal output current / phase
Total harmonic distortion
AC overvoltage category
5)
Current (inrush)
Maximum output fault current / duration
General data
Night-time power loss = standby consumption
European efficiency (580 / 800 / 930 V
Maximum efficiency
Safety class
EMC emission class
Pollution degree
Permitted ambient temperature
with built-in "AC disconnector" option
Permitted storage temperature
Relative humidity
Sound pressure level (580 V
Protection class
Dimensions (height x width x depth)
)
DC
/ 930 V
)
DC
DC
10 - 10000 kΩ
30 / 300 mA / ms
60 / 150 mA / ms
90 / 40 mA / ms
900 / 300 mA / ms
30 - 1000 mA
24 h
180 - 270 V
AC
1)
220 V
| 230 V
AC
AC
100 kW
100 kVA
1)
50 / 60 Hz
2)
0 - 1 ind./cap.
3~ NPE 380 / 220 V
AC
3~ NPE 400 / 230 V
AC
100 kW
100 kW
151.5 A / 144.9 A
< 3%
244 A peak /
4)
27.2 A rms over 3.2 ms
93.9 A / 22 ms
15 W
98.2 / 97.7 / 97.3%
98.5%
B
- 40 °C - +65 °C
-30 °C - +65 °C
- 40 °C - +70 °C
0 - 100%
74.4 / 79.3 dB(A) (ref. 20
µPA)
IP65
755 x 1109 x 346 mm
-
3
1
3
99