8 Configuration

The Alpha IP base station is configured via the Alpha IP room control unit Display, Display S, or via the
Alpha IP Access Point in conjunction with the Alpha IP app.

8.1 Configuration with Alpha IP room control unit Display (Display S)

Proceed as follows in order to configure the Alpha IP base station via the Alpha IP room control unit
Display (Display S):
1. Press and hold the setting wheel (E) in order to open the configuration menu.
2. Select the symbol "
If the room control unit is taught-in to more than one base station, select the desired base
station with the setting wheel.
The configuration menu for the Alpha IP base station includes device parameters "UnP1/UnP2" and chan-
nel parameters "ChAn", allowing to change lead and follow-up times for the pump, setback temperatures,
time intervals and many other parameters. The following table shows the available parameters:
UnP1:
Parameters
Antifreeze temperature
Pump control
Load equilibration:
Heating zones will be con-
trolled in a staggered way
if possible
Load collection:
Heating zones are
controlled collectively.
Actuator types:
NC - Normally Closed
NO - Normally Open
*If heating zone 1 is used as
pump control, it is necessary
to teach in a wall thermostat
to this heating zone, if an ad-
aptation of the pump parame-
ters shall be performed.
All manuals and user guides at all-guides.com
" and confirm the selection by shortly pressing the wheel.
Index
Value
P024
3
4
5
...
16 (default)
...
19
20
P025
0
1
2
3
4 (default)
5
6
7
Meaning
Antifreeze protection inactive
2.0 °C
2.5 °C
...
8.0 °C
...
9.5 °C
10.0 °C
active, with load equilibration,
actuator type NC
active, with load equilibration
actuator type NO
active, with load collection
actuator type NC
active, with load collection
actuator type NO
inactive, with load equilibration
actuator type NC
inactive, with load equilibration
actuator type NO
inactive, with load collection
actuator type NC
inactive, with load collection
actuator type NO
Configuration
29