Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

H-6508
HARD-WIRED EXIT SIGN
TOOLS NEEDED
Flathead Screwdriver
CAUTION! When using electrical equipment,
basic safety precautions should always be
followed, including:
• Do not use outdoors.
• Do not mount near gas or electric heaters.
• Do not let power cords touch hot surfaces.
• Use caution when servicing batteries. Avoid
possible shorting.
• Equipment should be mounted in locations
and at heights where it will not readily be
subjected to tampering by unauthorized
personnel.
BACK MOUNTING
1.
Drill 1/4" holes into oblong knock outs on back plate
that correspond to junction box holes to be used.
(See Figure 1)
Figure 1
Wire Nuts
EXIT Panel
PAGE 1 OF 6
1-800-295-5510
uline.ca
Phillips Screwdriver
INSTALLATION
Junction
Box
Back Plate
Plastic
Housing
Diffuser
Snap-in
Directional Arrow
SAFETY
• The use of accessories not recommended
by the manufacturer may cause an unsafe
condition.
• Do not use this equipment for anything other
than intended use.
• Before wiring to AC service, turn off AC power
at fuse or circuit breaker.
• Disconnect AC power and unplug battery
before servicing.
• Only use specified lamps in the fixture.
• Battery in this unit may not be fully charged.
After the AC service is supplied to the unit, let
the battery charge for at least 24 hours before
performing any tests.
2. Feed the transformer input leads through center
hole and make the proper connections. If using
120VAC, connect the black and white leads to the
building utility. If using 277VAC, connect the orange
and white leads to the building utility. Cap off
unused wire. If the unit is self-powered, be sure to
snap battery connector together.
3. Feed excess wire into junction box and secure back
plate to junction box. (See Figure 1)
4. Snap in arrows on EXIT panel as required. Then snap
EXIT panel to housing: top first, then bottom.
(See Figure 1)
NOTE: Use flexible
conduit only.
(See Figure 2)
Para Español, vea páginas 3-4.
Pour le français, consulter la pages 5-6.
Figure 2
0421 IH-6508
loading

Resumen de contenidos para Uline H-6508

  • Página 1 Para Español, vea páginas 3-4. Pour le français, consulter la pages 5-6. H-6508 1-800-295-5510 uline.ca HARD-WIRED EXIT SIGN TOOLS NEEDED Flathead Screwdriver Phillips Screwdriver SAFETY CAUTION! When using electrical equipment, • The use of accessories not recommended basic safety precautions should always be...
  • Página 2: Side Mounting

    (See Figure 7) Battery Use Manual Battery Test Switch on base of unit Connector Manual Battery to test. Red LED indicates normal operation. Test Switch Red LED (See Figure 8) Socket 1-800-295-5510 uline.com PAGE 2 OF 6 0421 IH-6508...
  • Página 3: Letrero "Exit" Con Cableado

    H-6508 1-800-295-5510 uline.ca LETRERO "EXIT" CON CABLEADO HERRAMIENTAS NECESARIAS Desarmador de Desarmador de Cruz Cabeza Plana SEGURIDAD ¡PRECAUCIÓN! Hay ciertas medidas básicas • El uso de accesorios no recomendados por que deben seguirse al utilizar equipos el fabricante podría causar situaciones no eléctricos, incluyendo:...
  • Página 4: Montaje Lateral

    Batería Interruptor Manual manual ubicado en la base de la unidad de Prueba de LED Rojo para hacer una prueba. El LED rojo indica un Batería Orificio funcionamiento normal. (Vea Diagrama 8) 800-295-5510 uline.mx PAGE 4 OF 6 0421 IH-6508...
  • Página 5: Outils Requis

    H-6508 1-800-295-5510 uline.ca ENSEIGNE DE SORTIE CÂBLÉE – « EXIT » OUTILS REQUIS Tournevis à tête plate Tournevis cruciforme SÉCURITÉ MISE EN GARDE! Lorsque vous utilisez de • N'utilisez pas cet équipement à d'autres fins l'équipement électrique, vous devez toujours que celles prévues.
  • Página 6: Fixation Au Plafond

    Utilisez l'interrupteur d'essai de batterie manuel sur Voyant à batterie manuel Emboîture DEL rouge la base de l'unité pour vérifier son fonctionnement. Le voyant à DEL rouge indique que l'unité fonctionne normalement. (Voir Figure 8) 1-800-295-5510 uline.ca PAGE 6 OF 6 0421 IH-6508...