3-Phase Power Supply Instruction Manual
Bedienungsanleitung für 3-Phasen Stromversorgung
1)
Technical Data
Output Voltage
Factory Setting at Full Load
Output Current
continuous
Output Current
for typical 4s
Output Power
continuous
Output Power
for typical 4s
2)
Output Ripple & Noise Voltage
AC Input Voltage
Input Frequency
3)
AC Input Current
3)
Power Factor
13)
Allowed Voltage Phase to Earth
EN 61000-3-2
4)
Input Inrush Current
3)
Hold-up Time
3)
Efficiency
3)
Power Losses
Operational Temperature Range
Output Derating
Storage Temperature Range
5)
Humidity
Vibration
Shock
Degree of Pollution (non-conductive) Verschmutzungsgrad (nicht leitend)
Degree of Protection
Class of Protection
Over-temperature Protection
Output Over-voltage Protection
7)
Touch (Leakage) Current
8)
Return Voltage Resistance
11)
Parallel Use
12)
Serial Use
9)
Dimensions
(WxHxD)
Weight
Approvals
Limited Warranty
1) All parameters are specified at 3x400Vac input voltage, symmetrical phase voltages, nominal
output current, "Single Use" setting, 25°C ambient and after a 5 minutes run-in time unless
otherwise noted.
2) 50-Ohm measurement, bandwidth 20MHz
3) at 3x400Vac / 3x480Vac, symmetric mains
4) Input inrush current electronically limited and is temperature independent.
5) Do not energize while condensation is present.
6) PE connection required (Ground).
7) Leakage current at 3x440Vac, 50Hz / 3x528Vac, 60Hz, TT/TN-mains
8) Loads such as decelerating motors and inductors can feed voltage back to the output of the
power supply. The figure represents the maximum allowed feed back voltage
9) Depth without DIN-rail.
10) See datasheet or markings on the unit.
11) Set jumper on the front to "Parallel Use". A fuse (or diode) on the output is required if more than
three units are paralleled.
12) Use only power supplies of the same type. The total output voltage should not exceed 150Vdc.
13) According to IEC 60664-1
Installation
Use DIN-rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm. Mounting
orientation must be output and input terminals on the bottom. For other orientations see
datasheet. Do not obstruct air flow as the unit is convection cooled. Ventilation grid must be kept
free of any obstructions. The following installation clearances must be kept when power supplies
are permanently fully loaded:
Left / right: 5mm (15mm in case the adjacent device is a heat source)
40mm on top, 20mm on the bottom of the unit.
Input Fuses
Internal input fuse: T6.3A (H.B.C.), not user accessible. The unit is tested and approved for
branch circuits up to 32A. An external protection is only required if the supplying branch has an
ampacity greater than this, however, in some countries local regulations might apply. Check local
codes and requirements. If an external fuse is necessary or utilized, minimum requirements need
to be considered to avoid nuisance tripping of the circuit breaker. A minimum value of 6A B- or 6A
C-Characteristic breaker should be used.
Terminals and Wiring
(see Fig. 6)
Use appropriate copper cables that are designed for a minimum operating temperatures of 60°C
(for ambient up to 45°C) and 75°C (for ambient up to 60°C). Follow national installation codes and
regulations! Ensure that all strands of a stranded wire enter the terminal connection! Up to two
stranded wires with the same cross section are permitted in one connection point (except PE
wire). Ferrules are allowed, but not required.
Input
2
Solid wire
0.5-6mm
2
Stranded wire
0.5-4mm
American wire gauge
20-10 AWG
Wire stripping length
7mm / 0.28inch
Tightening torque
0.8Nm / 7lb.inch
EMC Electromagnetic Compatibility
These power supplies are suitable for applications in industrial environment as well as in
residential, commercial and light industry environment without any restrictions. These devices
comply with FCC Part 15 rules. CE mark is in conformance with EMC directive 2004/108/EC as
well as the low-voltage directive (LVD) 2006/95/EC.
EMC Immunity: EN 61000-6-1, EN 61000-6-2
EMC Emission EN 61000-6-3, EN 61000-6-4, FCC Part 15 Class B
1)
Technische Daten
Ausgangsspannung
Werkseinstellung bei Nennlast
Ausgangsstrom
dauernd
Ausgangsstrom
für typisch 4s
Ausgangsleistung
dauernd
Ausgangsleistung
für typisch 4s
2
Ausgangswelligkeit
)
AC Eingangsspannung
Eingangsfrequenz
3)
AC Eingangsstrom
3)
Leistungsfaktor
13)
Erlaubte Spannung Phase zu Erde
EN 61000-3-2
4)
Einschaltspitzenstrom
3)
Pufferzeit
3)
Wirkungsgrad
3)
Verlustleistung
Betriebstemperaturbereich
Leistungsrücknahme
Lagertemperaturbereich
5)
Feuchte
Schwingen
Schocken
Schutzart
Schutzklasse
Übertemperaturschutz
Überspannungsschutz am Ausgang
7)
PE- Ableitstrom
8)
Rückspeisefestigkeit
11)
Parallelschaltbar
12)
Serienschaltbar
9)
Abmessungen
(BxHxT)
Gewicht
Zulassungen
Gewährleistung
Output
Signals
2
0.5-16mm
0.15-1.5mm
2
0.5-10mm
0.15-1.5mm
22-8 AWG
26-14 AWG
12mm / 0.5inch
7mm / 0.28inch
1.2Nm / 10.6lb.inch
Spring-clamp terminal
QT40.241
nom. DC 24-28V
"Single-Use", typ. 24.1V
nom. 40A (24V), 34.3A (28V)
nom. 60A (24V), 51.5A (28V)
nom. 960W
nom. 1400W
max. 100mVpp
nom. 3AC 380-480V -15%/+20%
nom. 50-60Hz
typ. 1.65A / 1.35A / Phase
typ. 0.88 / 0.9
nom. AC 480V
PFC-Norm Yes / Ja
typ. 4.5A peak
typ. 25ms / 25ms
typ. 95.3% / 95.2%
typ. 47.3W / 48.4W
nom. -25°C - +70°C
+60°C to +70°C 24W/°C
nom. -40°C - +85°C
IEC 60068-2-30 5 - 95% r.H.
IEC 60068-2-6 1g
IEC 60068-2-27 15g 6ms, 10g 11ms
EN 50178 / 62103 2
EN 60529 IP20
6)
IEC 61140 I
OTP Yes / Ja
OVP, max. 32Vdc
max. 0.68mA / 0.95mA
max. 35Vdc
Yes / Ja
Yes / Ja
nom. 110x124x127mm
max. 1500g
10)
Years / Jahre 3
1) Alle Werte gelten bei 3x400Vac Eingangsspannung, symmetrischer Phasenspannung,
Nennausgangsstrom, „Single-Use" Modus, 25°C Umgebung und nach einer Aufwärmzeit von 5
Minuten, wenn nichts anderes angegeben ist.
2) 50-Ohm Messung, Bandbreite 20MHz
3) bei 3x400Vac / 3x480Vac, symmetrisches Netz
4) Der Einschaltstromstoß ist elektronisch begrenzt und temperaturunabhängig.
5) Nicht betreiben, solange das Gerät Kondensation aufweist.
6) PE Verbindung erforderlich.
7) Ableitstrom bei 3x440Vac, 50Hz / 3x528Vac, 60Hz, TT/TN-Netze
8) Bremsende Motoren oder Induktivitäten können Spannung zum Ausgang des Netzteils
rückspeisen. Der Wert gibt die max. zulässige Rückspeisespannung an.
9) Tiefe ohne DIN-Schiene
10) Siehe Datenblatt oder Prüfzeichen auf dem Gerät.
11) Steckbrücke an der Front des Gerätes auf „Parallel Use" umstellen. Bei mehr als drei Geräten
wird eine Sicherung oder eine Diode zur Entkopplung benötigt.
12) Nur gleiche Geräte bis zu einer Gesamtspannung von 150Vdc
13) Gemäß IEC 60664-1
Installation
Geeignet für DIN-Schienen entsprechend EN 60715 oder EN 50022 mit einer Höhe von 7,5 oder
15mm. Der Einbau hat so zu erfolgen, dass sich die Eingangs- und Ausgangsklemmen unten
befinden. Für andere Einbaulagen siehe Datenblatt. Luftzirkulation nicht behindern! Das Gerät ist
für Konvektionskühlung ausgelegt. Es ist für ungehinderte Luftzirkulation zu sorgen. Folgende
Einbauabstände sind bei dauerhafter Volllast einzuhalten:
Links / rechts: 5mm (15mm bei benachbarten Wärmequellen)
Oben: 40mm, unten 20mm vom Gerät.
Sicherungen am Eingang
Das Gerät besitzt eine T6,3A (H.B.C.) Eingangssicherung, die nicht anwenderzugänglich ist. Das
Gerät ist geprüft und zugelassen zum Anschluss an Stromkreisen bis max.32A. Ein zusätzlicher
externer Schutz ist nur erforderlich, wenn der Speisestromkreis mit einem höheren Wert
abgesichert ist oder nationale Richtlinien es vorschreiben. Falls ein externes Schutzelement
verwendet wird, soll dieses nicht kleiner als 6A B- oder 6A C-Charakteristik sein, um ein
fehlerhaftes Auslösen zu vermeiden.
Anschlussklemmen und Verdrahtung
Verwenden Sie geeignete Kupferkabel, die mindestens für 60°C bei einer Umgebungstemperatur
bis zu 45°C und 75°C bei einer Umgebungstemperatur bis zu 60°C zugelassen sind. Beachten
Sie nationale Bestimmungen und Installationsvorschriften! Stellen Sie sicher, dass keine
einzelnen Drähte von Litzen abstehen. Bis zu zwei Leiter mit gleichem Querschnitt sind in einem
Anschlusspunkt zulässig (außer Schutzleiter). Aderendhülsen sind erlaubt, aber nicht erforderlich.
2
Starrdraht
2n
Litze
AWG
Abisolierlänge
Anzugsdrehmoment
EMV Elektromagnetische Verträglichkeit
Diese Stromversorgungen erfüllen die Anforderungen für Anwendungen in industrieller Umgebung
und für den Wohn-, Geschäfts- und Gewerbebereich ohne Einschränkungen. Die Geräte erfüllen
auch die Anforderungen der FCC Teil 15. Das CE Zeichen ist angebracht und erklärt die Erfüllung
der EMV Richtlinie 2004/108/EG wie auch der Niederspannungsrichtlinie 2006/95/EG.
Störfestigkeit: EN 61000-6-1, EN 61000-6-2
Störaussendung: EN 61000-6-3, EN 61000-6-4, FCC Part 15 Klasse B
QT40.481
DC 48-54V
48.0V
20A (48V), 17.8A (54V)
30A (48V), 26.7A (54V)
960W
1440W
100mVpp
3AC 380-480V -15%/+20%
50-60Hz
1.65A / 1.35A / Phase
0.88 / 0.9
AC 480V
Yes / Ja
4.5A peak
25ms / 25ms
95.4% / 95.2%
46.3W / 48.4W
-25°C - +70°C
24W/°C
-40°C - +85°C
5 - 95% r.H.
1g
15g 6ms, 10g 11ms
2
IP20
6)
I
Yes / Ja
60Vdc
0.68mA / 0.95mA
63Vdc
Yes / Ja
Yes / Ja
110x124x127mm
1500g
10)
3
(siehe Bild 6)
Eingang
Ausgang
2
2
0.5-6mm
0.5-16mm
2
2
0.5-4mm
0.5-10mm
20-10 AWG
22-8 AWG
7mm / 0.28inch
12mm / 0.5inch
0.8Nm / 7lb.inch
1.2Nm / 10.6lb.inch
Signale
2
0.15-1.5mm
2
0.15-1.5mm
26-14 AWG
7mm / 0.28inch
Federkraftklemme