Setup (cont'd)
Chain Mount
Requires: Exposed metallic conduit with the following
characteristics:
• 63.5 – 254 mm (2-1/2" – 10") in diameter
• capable of withstanding at least 22.3 kN (5000 lbs) of
force
Do not mount the pipe adapter to the
following:
• steel conduit less than 63.5 mm
(2-1/2") in diameter
• PVC conduit of any size.
These conduits will not support the
loads imposed by the puller.
Failure to observe this warning can
result in severe injury or death.
NO
When setting up the pipe adapter,
do not use the vise chains on a
structural support that is less than
51 mm (2") or more than 254 mm
(10") wide. An oversized or under-
NO
sized structural support can allow
the puller to slide or break loose and
strike nearby personnel.
Failure to observe this warning can
result in severe injury or death.
Install the vise chains properly.
• Follow the vise chain tightening instructions
carefully. Improperly tightened chains can allow
the puller to slide or break loose and strike nearby
personnel.
• Do not allow the vise chains to bind at the corners
when mounting the puller to a square or rectangu-
lar support. The vise chain must be uniformly tight
at all points.
Failure to observe this warning can result in severe
injury or death.
Greenlee / A Textron Company
®
Ultra Tugger
Cable Puller and Pulling Packages
37
Do not pull between the 10 o'clock and 2 o'clock
directions. Pulling between 10 o'clock and 2 o'clock
can damage the mounting conduit.
12
O'CLOCK
11
PULLING
10
ROPE
PULL
LOAD
9
SUPPORT
VISE CHAINS
O'CLOCK