Installation and Operating Instructions
SPECIFICATION
These installation and operating instructions
apply to the following SPIDER II temporary power
branch distribution system components. Do not
discard these instructions, save for future
reference.
PORTABLE SPIDER II POWER
DISTRIBUTION UNITS
Units are rated 60 amps, 120/208 VAC, Three
Phase, with 5 milliampere leakage current trip
level. Downstream protection is not provided
through the 60 amp outlet. The six 20 amp,
120 volt outlets are individually protected by
circuit breakers and GFCI circuit modules.
Model
20 Amp
Number
Receptacle (6)
SCTL0
TWIST LOCK
SCSB0
STRAIGHT BLADE
INTRODUCTION
Hubbell SPIDER II units equipped with Circuit
Guard
®
GFCI products, will protect you from
shock hazards resulting from ground faults.
Ground faults are current leaks and can result
in electric shock. Currents of only 60/1000 of
an ampere can be fatal. The GFCI protection
provided by Hubbell SPIDER II units
significantly minimizes shock hazards. Hubbell
SPIDER II products, which are listed by
Underwriters Laboratories as Class A, Group
I interrupters, respond to fault currents as low
as 5 milliamperes, and will shut off the current
th
within 1/40
of a second.
The SPIDER II provides ground fault protection
only for circuits to which it supplies power. The
SPIDER II does not protect its power supply
circuit or any circuits which are not supplied
from the Spider unit.
Wiring Device-Kellems
Hubbell Incorporated (Delaware)
Shelton, CT 06484
1-800-288-6000
www.hubbell-wiring.com
PD1869
01/12
II
®
English
The SPIDER II is designed to provide
protection against electrical shock hazards
due to line-to-ground faults. Although the
Circuit Guard Module does not limit the
magnitude of the fault current, and therefore
cannot prevent electric shock, it does limit the
duration of the shock to a period considered
safe for normally healthy persons.
Circuit Guard Modules will provide protection
against ground faults only. They will not protect
against overloads or short circuits. There is no
known device that will guard against the
electrical shock hazard resulting from
simultaueous contact with both the "hot" and
neutral wires of the electric circuit.
ELECTRICITY IS DANGEROUS. EVEN
WHEN SAFETY DEVICES ARE PRESENT,
HANDLE
WITH
CARE
AND
REASONABLE CAUTION.
LET CAUTION PREVAIL
The Hubbell SPIDER II is designed to be used on
a grounded electrical supply system. It will not
operate when supplied from a power source
which is not grounded. Over-current protection
of the proper rating, according to the National
Electrical Code, Article 240, must be used on
the supply circuit feeding the SPIDER II.
TEST PROCEDURE
All Models
Connect the SPIDER II unit to an appropriate
power source.
CAUTION
• Power is immediately available at the 60
amp outlet when the source is energized
on all SPIDER II models.
Note: The internal contactor will close after
an initial 1-2 second delay.
1. Verify all circuit breakers are in the "on"
position.
USE
®
Tabla de contenido
loading

Resumen de contenidos para Hubbell Spider II

  • Página 1 TWIST LOCK SCSB0 STRAIGHT BLADE LET CAUTION PREVAIL INTRODUCTION The Hubbell SPIDER II is designed to be used on Hubbell SPIDER II units equipped with Circuit a grounded electrical supply system. It will not Guard ® GFCI products, will protect you from operate when supplied from a power source shock hazards resulting from ground faults.
  • Página 2: Maintenance & Repair

    GFI SPIDER and Circuit Guard are registered trademarks of Hubbell Incorporated. (supply) side circuit: to trip. In the Hubbell SPIDER II system, 1.
  • Página 3: Diagramme De Câblage

    RAISONNABLES. TOUJOURS ÊTRE PRUDENT Numéro Prise (6) de modèle 20 ampères Le SPIDER II de Hubbell est conçu pour être utilisé SCTL0 TWIST LOCK avec un système d’alimentation électrique mis à SCSB0 LAME DROITE la terre. Il ne fonctionne pas s’il est alimenté par une source de courant qui n’est pas mise à...
  • Página 4: Maintenance Et Réparations

    (débranché) on conducteur neutre. Ce design annule l’effet de fuite à la terre SPIDER et Circuit Guard sont des marques de commerce déposées de Hubbell Incorporated. 3. Il y a un déséquilibre de tension excessif entre capacitive et il n’y a aucune limite théorique à la les circuits 1 et 2 de la ligne d’alimentation.
  • Página 5: Diagrama De Cableado

    El SPIDER II está diseñado para proteger contra individual GFCI. La unidad debe desengancharse. un año a partir de su compra. Hubbell reparará o reemplazará el artículo a su juicio en un plazo de 60 días. los riesgos de choque eléctrico debidos a las fallas 3.
  • Página 6: Desconexiones Inconvenientes

    2. Cualquiera de los conductores de alimentación provocando que se desconecte el GFCI. Sin SPIDER y Circuit Guard son marcas comerciales registradas de Hubbell Incorporated. (vivo) está abierto (desconectado) o conductor embargo, en el sistema SPIDER II de Hubbell, la de neutro.

Este manual también es adecuado para:

Sctl0Scsb0

Tabla de contenido