Refrigerant Piping Connection; Pipe Length And Additional Charge; Connection Instructions -Refrigerant Piping; Cut Pipe - AUX ASW-JA Instrucciones

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

REFRIGERANT PIPING CONNECTION

Pipe Length and Additional Charge

The length of refrigerant piping will affect the performance and energy efficiency of the unit. Nominal
efficiency is tested on units with a pipe length of 5 meters.
Refer to the table below for pipes requirements:
Pipes requirements (R32 refrigerant)
Model
09
12
18
24
When the outdoor unit is located more hight than the indoor unit, and the the drop height is more than
5 meters, you must install an oil trap in the gas line every 5 or 7 meters.
Connection Instructions –
Refrigerant Piping
Step 1: Cut pipes
When preparing refrigerant pipes, take extra care
to cut and flare them properly. This will ensure
efficient operation and minimize the need for
future maintenance.
1. Measure the distance between the indoor and
outdoor units.
Pipes
Max. Length
(m)
Liquid
Gas
20
1/4"
3/8"
1/4"
3/8"
20
1/4"
1/2"
25
25
3/8"
5/8"
Drop Height
Refrigerant
(m)
preload (m)
10
10
15
15
2. Using a pipe cutter, cut the pipe a little longer
than the measured distance.
3. Make sure that the pipe is cut at a perfect 90°
angle. Refer to Fig. 5.1 for bad cut examples.
90°
Oblique
93
6
Additional
refrigerant (g/m)
16
5
5
16
5
24
24
5
Rough
Warped
Fig. 5.1