4. SCHÉMAS DE CÂBLAGE
Schéma de câblage SA696.xx
LÉGENDE
1-2
SONDES DE NIVEAU OU FLOTTEUR MINIMAL
3-4
SONDES DE NIVEAU OU FLOTTEUR MAX1
5-6
FLOTTEUR MAX2 OU PRESSOSTAT START 1
7-8
FLOTTEUR MAX3 OU PRESSOSTAT EMERGENCE
9-10
FLOTTEUR ALARME OU PRESSOSTAT EMERGENCE
11
COMMUNE KLIXON MOTEURS
12
KLIXON MOT
13
KLIXON MOT
14
KLIXON MOT
15-16
ENTRÉE 4-20mA
17-18-19
SORTIE ALARME CONTACT PUR
CÂBLAGE AVEC TRANSDUCTEUR DE PRESSION
Max 10 mm²
0,8Nm
10 mm
CARTE D'EXPANSION
11 12 13 14
1 2
3 4 5 6 7 8
9 10
G.MIN G.MAX1 G.MAX2 G.MAX3
G.ALAR
PRES.1 PRES.2
PRES.3
EU
R 1
EU
R 2
EU
R 3
(MAX 5A)
- BLANC
+ MARRON
(M4)
10 mm
15 16
17 18 19
+ -
R
S
ANALOG
MOT1
4-20mA
ALARM
M
M
3
3
MOTEUR 1
MOTEUR 2
CÂBLAGE AVEC CAPTEUR DE NIVEAU PIÉZORÉSISTIF 4-20mA 4-20mA
Max 6 mm²
(M4)
2,5Nm
7
R
S
R
S
R
S
T
MOT2
MOT3
SUPPLY
M
3
MOTORE 3
8,3 mm
FRANCAISE
L1
L2
L3
LIGNE D'ALIMENTATION
400 Vac 50/60 Hz
- BLEU
+ ROUGE
Max 2.5 mm²
(M3)
0,5Nm