Vaporgard V2LM2 and V3LM2 LED luminaire
driver modules
Installation & maintenance information
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
APPLICATION
Vaporgard LED luminaires are suitable for use in the following hazardous (classified) areas as defined by the National Electrical Code (NEC
NEC/CEC:
UL standards:
• Class I, Division 2, Groups A, B, C, D
• UL844 – Hazardous (Classified)
• Class II, Division 1, Groups F, G (pendant, wall,
• UL1598 – Luminaires
stanchion mounting only)
• UL1598A – Marine
• Class II, Division 2, Groups F, G (junction box for
• UL8750 – LEDs
ceiling or wall mounting)
• Wet locations, NEMA 3, NEMA 4, marine
IEC Standards:
• IEC60079-0: 2017
ATEX/IECEx
• IEC60079-7: 2015
•
II 3G Ex ec IIC T* Gc Ta -30°C to 55°C
• IEC60079-31: 2014
•
II 3D Ex tc IIIB T* Dc Ta -30°C to 55°C IP66
•
II 3G Ex ec IIC T* Gc Ta -30°C to 40°C
CSA standard:
•
II 3D Ex tc IIIB T* Dc Ta -30°C to 40°C
• CSA C22.2 No. 137
• CSA C22.2 No. 250.0-08
*Note = See product nameplate for associated T-code.
WARNING
!
To avoid the risk of fire, explosion or electric shock, this product
should be installed, inspected and maintained by a qualified electrician
only, in accordance with all applicable electrical codes.
WARNING
!
To avoid electric shock:
Be certain electrical power is OFF before and during installation and
maintenance.
Wire in accordance with the NEC, CEC and local codes.
To avoid burning hands:
Make sure lens and housing are cool when performing maintenance.
INSTALLATION
1. Install mount:
a.
To install junction box (as ceiling mount or with wall mount): mark the
desired mounting location and drill holes for 1/4" or 6.5mm mounting
hardware (not supplied). Secure the junction box in place.
b.
To install wall mount bracket with junction box: place gasket supplied
against the flange of the wall mount. Align holes in the wall mount
with the tapped holes in the junction box, and insert the screws
supplied with the wall mount into the holes. Tighten screws to 30
lb.-in. (3.4 N-m).
Lubricate cable gland or conduit thread with Eaton's Crouse-Hinds
series HTL lubricant, and install conduit or cable gland to the hub. Pull
wires into the mounting module. Lubricate pipe plugs and close all
unused conduit entries. Tighten pipe plugs to 35 lb.-ft. (47.5 N-m).
c.
To install stanchion and pendant mount: lubricate hub thread with
Eaton's Crouse-Hinds series HTL lubricant. Thread the mount onto the
conduit until tight. Tighten set screw in hub using a 5/64" (2.0mm)
hex allen wrench (see Figure 2). Torque to 16 lb.-in. (1.81 N-m).
Pull wires into the stanchion mount or pendant cover.
2. Install adapter cover (for ceiling, stanchion and wall mounting)
a.
Pull wires through the center opening in the VLHR adapter cover. Slip
the keyhole slots in the VLHR adapter cover over the two (2) screws in
the mounting module (see Figure 1). Rotate the VLHR cover and snug
each screw. Torque each screw to 20 lb.-in. (2.3 N-m).
NOTE: The adapter cover is not intended to be removed following
installation.
IF 1885 • 12/19
Copyright © 2019, Eaton's Crouse-Hinds Division
IF 1885
®
):
Refer to the luminaire nameplate for specific classification
information, maximum ambient temperature suitability, and
corresponding operating temperature (T-code).
Vaporgard luminaire construction is designed for use indoors
and outdoors in marine and wet locations, where moisture, dirt,
corrosion, vibration and rough usage may be present.
Vaporgard may be wired as follows:
Input
Input
Series
Input voltage
power
current
V2LM2
UNV1
120-277 VAC, 50/60 Hz
0.35A
V2LM2
DC1
10-30 VDC
1.54A
V3LM2
UNV1
120-277 VAC, 50/60 Hz
0.35A
V3LM2
DC1
10-30 VDC
3.08A
TABLE 1 - Electrical Data Input
WARNING
!
To avoid explosion:
Make sure the supply voltage is the same as the luminaire voltage.
Do not install where the marked operating temperatures exceed the ignition
temperature of the hazardous atmosphere.
Do not operate in ambient temperatures above those indicated on the
luminaire nameplate.
Use proper supply wiring as specified on the luminaire nameplate.
All gasket seals must be clean and undamaged.
Before opening, ensure hazardous gases are not present. Electrical power
to the luminaire must be turned off. Keep tightly closed when in operation.
Keyhole
slot
Keyhole
slot
VLHR adapter
cover
FIGURE 1
3. Attach the LED housing:
a.
Hang the assembly on the hinge of the cover (see Figure 2).
b.
Connect cover ground lead with fork terminal to ground screw on LED
housing. Tighten ground screw (see Figure 3).
c.
Connect supply wires to the LED driver input leads per the appropriate
wiring diagram, using methods that comply with all applicable codes.
Tighten all electrical connections.
d.
Close LED housing onto cover, ensuring that wires are not caught
between the cover and the LED housing. Tighten three (3) screws
provided using a 3/16" (4.7mm) hex allen wrench (see Figure 4).
Torque to 30 lb.-in. (3.4 N-m).
To install to Vaporgard mounts specified in Figure 6:
NOTE: Vaporgard LED driver modules can be mounted to surface mounted VXF
or VXFT ceiling junction boxes, to VXT wall mount bracket, or to VXA stanchion.
1.
Loosen the mounting screws on the mount or the VXH adapter.
2.
Clean all debris from the luminaire mounting surface using mild soap
or a liquid cleaner such as Collinite NCF or Duco #7.
3.
Slip the keyhole slots of the VLHR adapter cover over the screws on
the mount. Twist the VLHR counterclockwise to lock it in place.
4.
Snug the two (2) screws, and then, in the same order, torque each
screw to 20 lb.-in. (2.3 N-m).
NOTE: The adapter cover is not intended to be removed following installation.
Output
current
14.7W
13.9W
29.4W
FIGURE 2
27.8W
DIMENSIONS
WALL
3 7/8
[99]
STANCHION
8 1/8
[206.7]
Page 1
IF 1885 • 12/19
5.
Attach the LED driver module housing.
a.
Hang the assembly on the hinge of the adapter module (see
Figure 3).
b.
Pull wiring into cover.
c.
Connect cover ground lead with fork terminal to ground screw
on LED housing. Tighten ground screw (see Figure 4).
d.
Connect supply wires to the LED driver input leads per the
appropriate wiring diagram, using methods that comply with
all applicable codes. Tighten all electrical connections.
e.
Close LED housing onto adapter cover, ensuring that wires
are not caught between the cover and LED housing. Tighten
three (3) screws provided using a 3/16 inch (4.7 mm) hex allen
wrench (see Figure 5). Torque to 30 lb.-in. (3.4 N-m).
LED housing internal ground screw
FIGURE 3
FIGURE 4
5 7/8
[149.1]
11 1/4
1 3/4
[285.1]
6 7/8
[44]
1
[175]
15/16
1/4
[25.4]
[23.9]
[5.6]
3/4" NPT HUB
1
1/2" REDUCER
SUPPLIED
[25.4]
1 3/4
[44]
4 3/4
[121.3]
1
8 3/4
[25.4]
[221.7]
11 13/16
Ø4 15/16
[299.9]
[125.2]
45°
1-1/4" HUB
8 3/4
[221.7]
Copyright © 2019, Eaton's Crouse-Hinds Division
FIGURE 5
1 3/4
[44]
7 1/16
[179.7]
1
[25.4]
1 3/4
[44]