JUNO FIREWALL
NEW CONSTRUCTION RECESSED HOUSINGS
ELECTRICAL CONNECTION
INSTRUCTIONS
Knock-
out
Quick
Connector
0-10V Dimming Wires
(-MVOLT models only)
Figure 6
Step 1. Provide electrical service according to national
and/or local electrical code to the wiring box located on
the fixture plaster frame. Supply wire insulation must
be rated for at least 90°C.
Step 2. Remove wiring box cover. Remove the
appropriate knock-out(s) to accommodate the type of
electrical supply being used (Fig. 6):
Metal Conduit. Remove appropriate round knock-
out(s) and connect conduit to wiring box with proper
connectors (not supplied).
12/2 or 14/2 Non-Metallic Sheathed Cable (Type
NM-B). Remove appropriate D-shaped cable knock-
out(s). Insert the NM-B cable through the cable trap
and make a 90˚L-shaped bend in cable as shown
(Fig. 7).
12/3 or 14/3 Cable (Type NM-B). Remove the
appropriate round knockouts and connect cable with
proper electrical connectors (not supplied and not
shown).
Step 3. Strip supply wire 3/8" and insert each supply
wire into appropriate connector. Connect black fixture
wire to hot, white fixture wire to neutral and green fixture
wire to ground. (Fig. 6).
Step 4. Place all wiring and connectors back in wiring
box and replace cover.
NM-B Cable
NM-B Cable
Knock-out
(D-Shaped)
NM-B Cable
Trap
(4 Places)
12/2 or 14/2 NM-B Installation
Figure 7
WARRANTY
5-year limited warranty. Complete warranty terms located at
Technical Services Phone 1-800-705-SERV (7378)
One Lithonia Way • Conyers GA 30010 • Phone 1-800-705-SERV (7378) • Visit us at www.acuitybrands.com/juno-recessed
©2020 Acuity Brands Lighting, Inc
INSTALLATION INSTRUCTIONS
FIRE RATED LED 4" IC1FW LEDT24
TM
FIXTURE DIMMING
IC1FW LEDT24 Downlights are dimmable with the use of most incandescent, magnetic low voltage or
electronic low voltage* wall box dimmers.
Consult Juno Product Services or website for compatibility.
*Electronic low voltage dimmers require a neutral wire connection in the wall box.
TRIM INSTALLATION
After ceiling is finished and painted, remove and discard paint shield from fixture. Electronically
connect the trim to the wiring from the housing using the orange connectors. For adjustable trims orient
trim as desired for proper aiming. Install trim into housing utilizing the trim push-in springs (Fig. 8).
JUNCTION BOX ACCESS BELOW CEILING
Before servicing, disconnect or switch off electrical supply to fixture. Failure to do so can result in
electrical shock and/or injury.
Step 1. Remove trim from fixture (Fig 8).
Step 2. Pull down inner housing to remove from fixture. Disconnect black and white wires connecting
inner housing and set aside (Fig. 9).
Step 3. Lift fire barrier flap on the side with wires protruding. The bottom of the flap will have a half
moon finger slot for easy lifting (Fig. 10). Before lifting the flap, make sure the wires are pushed out
of the wire slots provided in the flap to prevent tearing the fire barrier. This will allow access to the
LED driver (Fig. 11).
Step 4. Open junction box door inside of fixture by lifting black spring retention clip. Once junction
box door is released pull door out while slightly lifting to release lower mounting feet. Once free pull
plate towards fixture opening and rotate plate 90° so it will fit through fixture opening. Junction box
door rubbing against fire barrier is acceptable.
Step 5. Re-assemble fixture by completing steps 1 thru 4 in reverse order.
Figure 9
HALF MOON
FINGER SLOT
Figure 10
www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx
Rev 06/20
P4747
Orange Electrical
Connectors
Trim Push-In
Springs
Figure 8
Inner
Housing
Junction
Box
Figure 11
2 of 2