Technical Data; Dimensions - Messko MLog IM50 Instrucciones De Servicio

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

7

Technical data

7
Technical data
Housing:
Materials:
Basic housing: Luran S,
Protectors: Softell TKS,
resistant to weathering and
aging, good resistance to
chemicals

Dimensions:

297 mm x 196 mm x 59 mm
Mounting:
4x through-hole M8
Display and operating elements:
Display (IM100):
LCD display, black/white,
128 x 128 pixel, transreflective
Status LEDs:
1x green "ACTIVE",
1x yellow "BATTERY",
1x red "EVENT/ALARM"
Push-button:
IM100: 10 push-buttons,
contacts stainless steel, gold-
plated
IM50: 2 push-buttons, contacts
stainless steel, gold-plated
Software:
MLog
Power supply:
Battery type:
6x LR14, C cell, alkaline (Zn-
MnO2)
Nominal voltage:
1 .5 V per cell
Capacity:
Min . 7800 mAh
Measured value for acceleration:
Sensor type:
3-axis acceleration sensor
Measuring range:
± 16 g in X, Y and Z direction
Accuracy:
see diagram below
Sampling rate:
1 .6 kHz
Resolution:
0 .1 g
Measured value for temperature:
Measuring range:
-40 °C . . . +125 °C
Accuracy:
± 1 °C (measuring range -20° C
. . . +80 °C)
Resolution:
± 0 .1 °C
Measured value for relative humidity:
Measuring range:
0 . . . 100%rH
Accuracy:
± 3%rH (measuring range
20%rH . . . 80%rH)
Resolution:
± 1%rH
Digital inputs (optional) (only IM100):
Number:
max . 2 inputs
Signal voltage "0":
< 0 .8 V
Signal voltage "1":
> 2 .4 V
Scanning frequency:
adjustable from 10 ms
Universal inputs (optional) (only IM100):
Number:
max . 6 inputs
Nominal voltage:
0-5 V DC
BA3431002/04 ES-EN
Analyser
®
Resolution:
12bit A/D converter
Measuring error:
0 .2% of the measuring range
end value
Internal resistance:
> 10 kΩ
Scanning frequency:
Adjustable from 10 ms
Data memory:
Activation time:
< 1 ms
Time:
Coordinated Universal Time
(UTC), date/time
Storage medium:
non-volatile EEPROM
Event memory:
125,000 events (64 byte/
event)
Shock memory:
400 shock events (1 .9 s/
shock)
Shock filter:
adjustable from 1 to 1000 ms
(0 ms = no filter active;
all values will be stored)
Ports:
USB:
mini USB, B type
Bluetooth:
version 2 .1 + EDR, range
about 10 m, optional, only IM100
GSM module (optional) (only IM100):
Protocols:
GSM/GPRS/EDGE
Frequencies:
quad-band, 850/900/1800/
1900 MHz
Transmitting power:
class 4 (2W@850/900 MHz),
class 1 (1W@1800/1900 MHz)
GPS module (optional):
Transmission values: Longitude & Latitude, globally
Operating conditions:
Class of protection:
IP 65
Ambient temperature: -40 °C . . . +80 °C
Weight:
1 .8 kg
29
Tabla de contenido
loading

Este manual también es adecuado para:

Mlog im100

Tabla de contenido