Temper CS-INV-S-METER Manual De Instrucciones página 14

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

CS-INV-S-METER
Application
The energy-meters "with a white back-lighted LCD screen for prefect reading" are used to measure single-phase
like residential, utility and industrial application. The unit measures and displays various important electrical
parameters, and provide a communication port for remote reading and monitoring. Bi-directional energy
measurement makes the unit a good choice for solar PV energy metering.
PART 1 Specification
General Specifications
Voltage AC (Un)
Voltage Range
Base Current (Ib)
Max. Current (Imax)
Mini Current (Imin)
Starting Current
Power Consumption
Frequency
AC Voltage Withstand
Impulse Voltage Withstand
Overcurrent Withstand
Pulse Output Rate
-Pulse Output 1
-Pulse Output 2
Display
Max. Reading
Accuracy
Voltage
Current
Frequency
Power factor
Active power
Reactive power
Apparent power
Active energy
Reactive energy
230V
176~276V AC
10A
100A
0.5A
0.4% of Ib
<2W/10VA
50/60Hz(±10%)
4KV for 1 minute
6KV-1.2uS waveform
30 Imax for 0.01s
1000/100/10/1 imp/Exp/kWh/kVArh (configurable)
1000imp/kWh (default) for import kWh
LCD with white backlit
999999.9 kWh/kVArh
0.5% of range maximum
0.5% of nominal
0.2% of mid-frequency
1% of Unity
1% of range maximum
1% of range maximum
1% of range maximum
Class 1 IEC62053-21
Class B EN50470-1/3
Class 2 IEC62053-23
Bidirectional energy meter - Single-phase system