Electrical And Wiring; Electrical Data; Recommended Fuse And Cable Sizes - Acson international 5ACV 100 CR Manual De Instalación

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 48
Do not allow water remain in the water pipes if the unit is not operating for a long period.
Water must be drained out if the unit is not running during winter. Failing to do so would cause the pipe to crack.
Do not drink the chilled water in the unit.
Refer to the wiring diagram provided on the unit when making electrical wiring.
Do not ground any electrical equipment to the water piping.
Table B-1 : R410A - Heat Pump
Model
Power supply
Voltage range
Nominal Power Input (Cooling/Heating)
Nominal Current Input (Cooling/Heating)
Compressor Maximum Continous Current
Compressor Full Load Current (FLA)
Compressor Locked Rotor Current (LRA)
Pump Power Input (Cooling/Heating)
* Readings taken at rated compressor frequency. The Power Input and Current differ depending on the combination of
outdoor temperature and entering water temperature. For further details, please refer to Technical Manual.
Heat Pump
Model
Voltage Range **
Recommended Fuse *
Power Supply Cable Size *
Number of Conductor
Interconnection Cable Size *
IMPORTANT : * The figures shown in the table are for information purpose only. They should be checked and selected to
comply with the local/national codes of regulations. This is also subject to the type of installation and
conductors used.
** The appropriate voltage range should be checked with label data on the unit.
All manuals and user guides at all-guides.com
PRESSURE GAUGE
GATE
GATE
VALVE
VALVE
GATE
BALANCING
THERMOMETER
VALVE
VALVE
FLEXIBLE
GATE
THERMOMETER
VALVE
FLEXIBLE
! ! ! ! ! CAUTION

ELECTRICAL AND WIRING

ELECTRICAL DATA

5ACV100CR
V-ph-Hz
V
W
12 / 11.4
A
24.4 / 23.9
System 1* System 2 System 1* System 2 System 1(inv)*System 1System 2
A
21.0
A
16.4
A
W
1013 / 1026

RECOMMENDED FUSE AND CABLE SIZES

5ACV 100 CR
A
40
mm
2
10
5
mm
2
1.5
1-3
AIRVENT (INSTALL
HIGHEST POSITION)
PRESSURE
DIFFERENTIAL
BALANCING
GATE
VALVE
VALVE
VALVE
STRAINER
GATE VALVE
CHECK
(LOWER POSITION
VALVE
FOR DRAINAGE)
MAKE UP
VALVE
5ACV135CR
400 / 3 / 50
380-415
15.8 / 16.3
30.0 / 31.1
13.7
21.0
26.0
11.1
18.6
16.6
67
111
882 / 907
5ACV 135 CR
380 – 415V /3Ph /50Hz + N + !
60
10
5
1.5
FAN COIL UNIT/AIR HANDLING UNIT
Figure 2
5ACV210CR
23.2/22.9
38.5/38.1
21.0
17.0
29.0
16.4
10.7
22.2
90
118
1175/1294
5ACV 210CR
100
10
5
1.5
Tabla de contenido
loading

Este manual también es adecuado para:

5acv 135 cr5acv 210 cr

Tabla de contenido