For these single conduit filters with return supply, the piping can be vented during start-up by
activating the ventilation valve
• Push the connection hose onto the nozzle, open the ventilation valve.
Once the filter element
no more air escaping from the connection hose:
• Close the ventilation valve
• Remove the connection hose
If the fill level in the filter cup drops or it runs empty then there is a leak in the system.
SHUT-DOWN immediately!
Fuel oil consumer installations should be checked for perfect condition by a specialist
company, or specialist company under water law where applicable, before initial start-up.
Fuel oil consumer installations which do not satisfy the TRÖl requirements may not
be started up.
Filter cup partially filled
Air and volatile oil components can evaporate out of the operating medium from an air / gas
cushion in the filter cup and accumulate in front of the moistened filter element. Particular
attention should be paid to this when using single conduit filters and low flow rates. The
interior of the filter element, which cannot be seen, is however still completely filled with
operating medium so that a filter cup which is only partially filled with operating medium has
no effect on safe operation.

OPERATION

• Use this product only when you have carefully read the assembly and operating
manual.
• For your own safety, observe all the safety messages in this assembly and
operating manual.
• Please also consider the safety of others.
Operation of the shut-off fitting
The handwheel on the shut-off fitting
of the system. During extended shut-down periods or MAINTENANCE work, the handwheel
on the shut-off fitting
Handwheel on the
shut-off fitting

MAINTENANCE

The following is recommended during the course of annual maintenance or after extended
SHUT-DOWN periods:
• Leak testing of the filter including connections.
• Visual inspection of the plastic filter cup
deformations.
• Replacement of the filter element
12 / 16
Single conduit filter and double conduit filter with plastic filter cup
Ventilation valve with connection hose:
:
in the filter cup
firmly
is set to the CLOSED position.
turn anticlockwise to the
, see REPLACEMENT.
is surrounded by operating medium and there is
is set to the OPEN position during ongoing operation
OPEN
stop
+
for possible damage, e.g. cracks or
CLOSED
turn clockwise to the stop
Part no. 13 852 51 a