Grohe Agira 20 425 Guia De Inicio Rapido página 5

Tabla de contenido
Application
Operation is possible in conjunction with:
- Pressurized storage heaters
Operation is not possible with:
- Low-pressure storage heaters (displacement water heaters)
Specifications
• Max. flow
• Flow pressure
- min.
- recommended
- greater than 72.5 psi, fit with pressure reducing valves
• Max. operating pressure
• Test pressure
• Temperature
- max. (hot water inlet)
• Water connection
Note
Major pressure differences between cold and hot water supply
should be avoided.
Installation
Refer to the dimensional drawing on Page 1.
Flush piping system prior and after installation of faucet
thoroughly!
Side valves, see Fig. [1].
• Valve with a groove on the top edge of the cartridge (A)
should be mounted on the right (cold water) side.
• Valve without a groove on the top edge of the cartridge (A)
should be mounted on the left (hot water) side.
1. Screw the mounting set (B) to the bottom of the thread of the
side valve (C).
2. Insert the side valve (C) through the basin hole from below.
3. Close the cartridges (clockwise for the hot side and counter-
clockwise for the cold side).
4. Slide on o-ring (D) and screw on escutcheon (E).
5. With 28mm open-ended spanner fasten the side valve (C).
The distance between the top of the cartridge and the basin
must be 2 1/8".
6. Close the cartridges (clockwise for the hot side and counter-
clockwise for the cold side).
7. Push complete lever (F) down to the side valve (C) be sure
that the lever (F1) points away from the spout and secure by
screwing only the sleeve (F2) on the escutcheon (E).
All manuals and user guides at all-guides.com
English
5.7 L/min or 1.5 gpm/60 psi
7.25 psi
14.5 - 72.5 psi
145 psi
232 psi
176 °F
cold - Right hand
hot - Left hand
Spout, see Figs. [2], [3], [4] and [5].
1. Place the O-ring (G) on the basin and insert the spout (H)
from above, see Fig. [2].
2. Place the mounting set (I) against the bottom of the basin
and fasten.
Tighten hexagon nut with a 13mm socket wrench.
3. Mount in clip (J), see Fig. [3].
4. Connect flexible hoses (K) to the side valves, see
Figs. [3], [4] and [5].
Mount lift rod and pop-up drain, see Fig. [5] and [6].
1. Insert the lift rod (L) through the spout, see Fig. [5].
2. Fit pop-up drain (M).
Ensure that flange of pop-up drain is sealed, see Fig. [6].
Connect faucet
Connect the side valves to the water supply. Insure the
supplied washers are used for all connections.
The cold water supply should be connected on the right side
and the hot water supply to the left valve.
Open cold and hot water supply and check connections
for leakage!
Maintenance
Inspect and clean all parts, replace as necessary and grease
with special grease.
Shut off cold and hot water supply.
I. Ceramic cartridge, see Fig. [7].
Secure side valve against sliding back.
1. Pull off lever (F).
2. Unscrew the ceramic cartridge (A) using a 15mm wrench.
3. Change complete ceramic cartridge (A) or O-ring (A1).
Observe the different replacement part numbers of the
cartridges.
II. Flow control, see Page 2.
Unscrew and clean flow control (13 351).
Assemble in reverse order.
Replacement parts, see Page 2 ( * = special accessories).
Care
Instructions for care of this faucet will be found in the Limited
Warranty supplement.
4
Tabla de contenido
loading