MORDOMUS iDL64 Manual De Instrucciones página 2

Idiomas disponibles

Idiomas disponibles

EN
iDL64 – Interface compatible with DALI
Bus
Features:
Interfaces with DALI Bus.
MdiBus interface.
DIN Rail Distribution Board mounting.
Applications:
Control of up to 64 output devices.
Specifications:
Power supply Voltage: 15VDC;
Consumption: 30mA @ 15VDC;
DALI Bus max. Voltage: 22,5VDC.
DALI Bus max current: 250mA.
Storage Temperature: -10ºC to 60ºC;
Operating Temperature: 10ºC to 50ºC;
Maximum humidity: 80% non-condensing;
Physical Specifications:
Dimensions: 52mm x 90mm x 70mm, mounting on DIN rail (3
modules);
Protection degree: IP20, for indoor use;
Self-extinguishing plastic box UL-94 V0;
Compatibility:
Compatibility with iThink module: V1.0 or higher.
Compatibility with Mordomus software: Mordomus iThink
V2020.1 or higher.
ATTENTION:
Never open the housing.
Never remove the circuit board from its housing.
Never crimp or cut cables while they are connected
to powered equipment.
The module is not provided with additional protection
against short circuit, therefore it is recommended to
use a power supply with the correct specifications.
Mordomus shall not be liable for any damages
resulting from the use of our equipment outside the
specifications and/or for a purpose other than that
intended.
When using a low cross section cable there might be
voltage drops that could force the module into under-
voltage protection mode.
Do not connect power supplies with an output current
greater than 4A.
The power supply shall never be connected to the
modules at the extremities of the bus as in
Do not connect more than 64 Dali devices on the Dali
iDL64
Bus.
The Mordomus power supply shall be connected to a
central module in order to distribute the power to the
remaining modules. For larger installations add as
many power supplies as required, always respecting
a uniform distribution. View
Overview:
MdiBus In connector
MdiBus Out connector
Power Supply iPSE154 (15V 4A)
Addressing Button
Power supply connector 15VDC 2,1x5,5mm
Dali Bus connector
Connections:
Specification and cross section of conductors:
MDiBus Circuit - CAT 6 UTP;
MDiBus connection: To connect the module to the MDiBus a CAT
6 UTP cable with RJ45 connectors according to EIA568A or
EIA568B standards must be used.
15VDC Power supply: It is recommended to use the iPSE154
power supply. The iDL64 module can source its power from other
nearby modules through the MDiBus cable.
Dali Bus: It is recommended to use mains rated wiring for the Dali
bus connections. The recommended wire cross section is at least
1,5mm^2. When using the maximum bus current over maximum
distance, a wire cross section of 2,5mm^2 might be necessary. No
voltage drops larger than 2V along the bus are allowed by Dali
specifications. A Dali compatible power supply must be used
(Mean-Well DLP-04R or other).
The network can be arranged in bus or star topology, or a
combination of these. When using the maximum distance for the
Dali Bus it is advised to avoid routing the bus conductors adjacent
to any mains power conductors.
Enrollment:
To enroll the iDL64 module proceed as follows:
1.
Make sure that the iDL64 is powered by a suitable
power supply
and connected to the MdiBus
.
figure
2.
2.
In the Mordomus software access the menu
Configurations
and
HW 1.0
Modules/Addresses.
3.
On the iDL64, press and hold the addressing button
for at least 1sec. The green LED will blink slowly
until the addressing is complete.
Figure
3.
4.
The iDL64 should be added automatically to the list
and the green LED should stop blinking.
Commissioning:
With all Dali devices installed and powered click on the button
Commissioning that can be found in the Mordomus Software
under Configurations → Modules/Addresses, double-clicking the
device iDL64. The commissioning might take up to about 3
minutes. Now all devices should be controllable from within the
Mordomus Software. If no devices respond, shortly interrupt the
power supply of the Dali Bus and all control gears.
In case of more than one control gear responding to the same
address, perform the Commissioning procedure once more.
Note: The iDL64 configures the connected control gear's outputs
to remain in off state on power on and bus failure conditions.
Reset:
To perform a reset to the module, interrupt the 15VDC
power supply for 5 seconds.
LED codes:
Green LED ON: Module powered and enrolled to software;
Red LED ON: Module powered and not enrolled to software;
Green and Red LEDs blinking simultaneously: Under-voltage
protection mode. Power supply voltage is to low;
Green LED blinking continuously: Module awaiting address
definition;
Red LED flashing: Module sending/receiving data.
Note: The light of the green and red LEDs is visible through the
grid of the plastic enclosure.
This product complies with the Electromagnetic
Compatibility Directive 2014/30/EU.
This product conforms with the EU Directive 2011/65,
RoHS
regarding the restriction of use of certain hazardous
substances in electric and electronic devices.
For EU countries only.
All old electrical and electronic devices must be
separated from normal household waste and disposed
of at designated facilities. For further information
contact your local authorities, waste disposal office or
the shop where you bought the device.
-----------------------------------Disclaimer---------------------------------------
This product is neither certified or approved by the DALI Alliance.
All product names, logos, and brands are property of their
respective owners. The use of the term "DALI" is solely intended to
inform about certain compatibilities and no endorsement is implied.
access
the
sub-menu
http://mordomus.com/mordomus/docs/ithink/iDL64.pdf
PT
iDL64 – Interface compatível com Dali
Bus
Caraterísticas:
Aplicações:
Especificações:
Tensão Alimentação: 15VDC;
Consumo: 30mA @ 15VDC;
Tensão máx. barramento Dali: 22,5VDC.
Corrente máx. barramento Dali: 250mA.
Temperatura Armazenamento: -10ºC a 60ºC;
Temperatura Funcionamento: 10ºC a 50ºC;
Humidade máxima: 80%, sem condensação;
Especificações Físicas:
Dimensão: 52mm x 90mm x 70mm, fixação em calha DIN (3
Módulos);
Grau de Proteção: IP20, para uso no interior.
Caixa em plástico auto extinguível UL-94 V0;
Compatibilidade:
Compatibilidade com o módulo iThink: V1.0 ou superior.
Compatibilidade com Software Mordomus: Mordomus iThink
V2020.1 ou superior.
ATENÇÃO:
v.2103
Interligação com barramento Dali.
Interface MdiBus;
Montagem em calha DIN.
Controlo de 64 dispositivos de saída.
Nunca abrir a caixa de suporte de calha DIN.
Nunca remover a placa de circuito impresso da
caixa.
Nunca cravar fichas ou cortar os cabos enquanto
estes
estiverem
conectados
a
equipamentos
alimentados.
Os módulos não são providos de proteção adicional
contra curto circuito, recomenda-se por isso o uso de
fontes de alimentação com as especificações
corretas.
2/5