INSTALLATION INSTRUCTIONS
WOS-M2R/WOS-MN2R
WOS-M2R
PIR Sensor
WOS-MN2R
PIR Sensor
DESCRIPTION
The WOS-M2R/WOS-MN2R are line voltage powered wall switch occupancy
sensors. They turn lighting systems on and off based on occupancy. The
sensor is configured to turn lighting on, and hold it on as long as the sensor
detects people moving in the room. After no movement is detected for a user
specified set time (5 to 30 minutes), the lights are switched off.
Optional energy savings features are included. The "walk-through" mode
shortens turns off timing to 3 minutes when no activity is detected after 30
seconds. An integral light sensor can keep lights off if sufficient daylight
is present in the room. Each relay may be set with a separate light level
activation point to create a two stage control.
An optional setting for bathroom fan operation is available. Set one relay
with a longer delay time. Light will turn off but fan will continue to run.
SPECIFICATIONS
VOLTAGE: 120/230/277 VAC
OPERATING TEMPERATURE: 32° to 131°F (0°to 55°C)
ADJUSTABLE TIME DELAY: 5 minutes - 30 minutes (software settable)
WALK-THROUGH MODE: 3 minutes if no activity after 30 seconds
(software settable)
TEST MODE: Software setting
PIR COVERAGE: SENSITIVITY ADJUSTMENT - Software settable
COVERAGE: 1200 sq. ft.
CAUTION
We recommend that installation be made by a liscensed electrician.
Before wiring and servicing, power to this unit and the
equipment it controls must be turned off at the main panel. Connect in
accordance with national and local electrical codes.
WARNING
Unit must be properly grounded to operate correctly.
WIRING INSTRUCTIONS: WOS-M2R
1. Turn power off at the electrical panel.
2. Connect the sensor black wire to line. Connect the sensor red wire for relay #1 (right hand side) to the
load #1. Connect the sensor blue wire for relay #2 (left hand side) to the load #2.
3. Connect the green wire to the ground. Unit must be properly grounded.
4. Mount the sensor to electrical box using 2 mounting screws provided.
5. Install wall plate.
6. Turn power on at the electrical panel.
7. Program only if custom setting is desired. Refer to the push button chart and follow FOUR & OUT THE
DOOR instructions.
BLUE
WIRING INSTRUCTIONS: WOS-MN2R
1. Turn power off at the electrical panel.
2. Connect the sensor black wire to line. Connect the sensor white to neutral. Connect the sensor red wire
for relay #1 (right hand side) to the load #1. Connect the sensor blue wire for relay #2 (left hand side)
to the load #2.
3. Connect your system grounding wire to the green screw on the sensor. Unit must be properly grounded.
4. Mount the sensor to electrical box using 2 mounting screws provided.
5. Install wall plate.
6. Turn power on at the electrical panel.
7. Program only if custom setting is desired. Refer to the push button chart and follow FOUR & OUT THE
DOOR instructions.
BLUE
FOR TECHNICAL SUPPORT: [email protected] 888.500.4598
COVERAGE PATTERN
The WOS-M2R/WOS-MN2R provides a pattern of 1200 square feet. The diagram shows motion
detection area with small motion detection closer to the sensor. Barriers within the space that
block line-of-sight to sensor detection will decrease coverage area.
PLACEMENT GUIDELINES
The sensor should be installed with a visually unobstructed view of the workspace normally
occupied. If the occupant cannot see the sensor from their normal work position, the sensor will
not be able to detect their presence. File cabinets, doors, partitions, or walls are typical types of
obstructions.
Avoid sensor placement with a view through a doorway. If doorway view is unavoidable, set
sensor to manual move (vacancy setting) with function 6.
LI-960(A)
loading

Resumen de contenidos para Tork WOS-M2R

  • Página 1 WIRING INSTRUCTIONS: WOS-M2R COVERAGE PATTERN The WOS-M2R/WOS-MN2R provides a pattern of 1200 square feet. The diagram shows motion 1. Turn power off at the electrical panel. detection area with small motion detection closer to the sensor. Barriers within the space that 2.
  • Página 2: Installation Instructions

    FOUR & OUT THE DOOR SETTINGS CHANGE To change a program feature: INSTALLATION INSTRUCTIONS PREP: Review the function to see the function number, current setting and new setting that is to be entered. 1. START program mode: PUSH BUTTON FUNCTION CHART a.
  • Página 3 INSTRUCTIONS DE CÂBLAGE: WOS-M2R MODÈLE DE COUVERTURE La WOS-M2R/WOS-MN2R fournit un modèle de 1 200 pieds carrés. Le diagramme montre 1. Coupez l’alimentation électrique au panneau électrique la zone de détection de mouvement avec une détection de mouvement réduit plus près du 2.
  • Página 4 Modification des paramètres FOUR & OUT THE DOOR Pour modifier une fonctionnalité du programme: INSTRUCTIONS D'INSTALLATION PRÉPARATION: Revoyez la fonction pour voir le numéro de la fonction, le réglage actuel et le nouveau réglage à introduire. 1. LANCER le mode de programmation: DIAGRAMME DE FONCTIONS DES BOUTONS-POUSSOIRS a.
  • Página 5: Especificaciones

    INSTRUCCIONES DE CABLEADO: WOS-M2R PATRÓN DE COBERTURA La serie WOS-M2R/WOS-MN2R proporciona un patrón de 1200 pies cuadrados. El diagrama 1. Apague la corriente en el panel eléctrico. muestra el área que tiene detección de movimiento con la detección de poco movimiento más 2.
  • Página 6 CAMBIO DE AJUSTES CUATRO Y SALIDA Para cambiar la función de un programa: INSTRUCCIONES DE INSTALACIÓN PREP: Revise la función para ver el número de la función, el ajuste de corriente y el nuevo ajuste que debe colocarse. 1. INICIAR el modo de programa: TABLE DE FUNCIONES DE LOS BOTONES a.

Este manual también es adecuado para:

Wos-mn2r