Accessories - WIK GA11 Manual De Instrucciones

Analizador para determinar la calidad del gas aislante
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

11. Specifications / 12. Accessories
N₂ percentage sensor (SF₆ in N₂)
Measurement principle
Measuring range/accuracy
Optional sensor technology
Oxygen sensor
Measurement principle
Measuring range/accuracy
Permissible air humidity
Max. zero offset
Long-term stability
Service life
±
1)
0.5 % at 0 ... 25 %, for special calibrations the measuring tolerances may deviate from the standard specification.

12. Accessories

WIKA operating instructions analytic instrument, model GA11
Sound velocity
0 ... 100 % vol. ±0.5 % vol.
Optical
0 ... 10 % vol. ±0.3 % vol. (option: 0 ... 25 % vol.)
15 ... 90 % r. h. (non-condensing)
0.2 % vol.
< 2 % signal degradation/month (linear)
2 years starting from installation
Description
Gas recovery bag, model GA45
Low weight and easily transportable
Cost-effective version to prevent SF₆ gas emissions
Compatible with all WIKA gas analytic instruments
With overpressure valve as burst protection
Resistant to decomposition products
Storage capacity 110 litres
For further specifications see data sheet SP 62.08
Precision pressure sensor 0 ... 10 bar abs.
O₂ sensor
1)
Order number
14013015
14243981
14404180
37
EN
Tabla de contenido
loading

Tabla de contenido