technical data
c output power:
v Pulsar CT 3:
v Pulsar CT 6:
v Pulsar CT 12:
c utility power:
v voltage (V):
v frequency (F):
c output specifications:
v voltage (V):
v frequency (F):
v total harmonic distortion:
c environment:
v disturbances:
v susceptibility:
v insulation class:
v response time:
v limit operating temperatures:
v automatic limitation of load current to:
v safety standards:
v protection index:
c dimensions and weights:
v height (mm):
v width (mm):
v depth (mm):
v weight (kg):
8
315VA/250W
625VA/500W
1250VA/1000W
230V ±20% single phase
50Hz
230V single phase (±5% for 230V±20% utility power, ±3% for 230V±15% utility power)
50Hz
< 3% at rated load
NFC EN 50091-2 and 50022/11-B
NF EN 50091-2 and IEC 1000-4-2 to 1000-4-5
H (NFC 52200)
30 ms
-10°C, +40°C
2 In max. (this limitation must be of short duration)
CEI 950 / NF EN 60950 / NF EN 50091-1
IP20 (NFC 20010)
Pulsar CT 3
Pulsar CT 6
253
253
172
172
400
400
10
15
Pulsar CT 3 / 6 / 12: 51032617XT/AA
Pulsar CT 12
253
172
400
25
Merlin Gerin by MGE UPS SYSTEMS