Technical Data - Kaco RS485 Manual Del Usuario

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 12
4. The damage report must be received by the shipping company in writing within
six days following receipt of the component. We will be glad to help you if ne-
cessary.

Technical Data

Requirement for RS485 overvoltage pro-
tection
RS485 overvoltage protection base element 3012741 RS485
1 x overvoltage protection module plug
Install RS485 overvoltage protection
↻ NOTE: Lack of voltage and current ensured on the PV inverter.
1 Unfasten the housing cover of the PV inverter using the 6 screws and remove
carefully [
T_25]
2 Open the packaging of the RS485 SPD kits and remove components.
NOTE: Clamp the RS485 base element for overvoltage protection at the inten-
ded position in accordance with the drawing on the top hat rail from bottom
to top.
3 The following colour coding must be observed for the internal/external RS485
cable:
Data A => white (WH); Data B => blue (BU); GND => violet (VT)
4 The internal RS485 cable is to be connected to the overvoltage socket on the
socket.
NOTE: For the input/output on the RS485 externally the output of the over-
voltage protection socket should be assigned twice.
5 Insert the RS485 cable through the interface cable fitting in the connection
area.
6 Strip the RS485 cable [approx. 20 mm] and remove the insulation from the in-
dividual wires [8 mm].
7 Fit wires with wire sleeves and clamp onto the RS485 base element according
to the connection diagram [ S_M3 /
8 Connect the output cable with RS485 plug (included with the overvoltage kit)
to the RS485 base element and insert the RS485 plug into the RS485 socket on
the communication board.
9 Fix the output cable to the cable guide.
Page 4
Modules (KACO art. no.)
3012742 RS485
0,5 Nm ].
RS485 overvoltage protection on blueplanet 87.0-165TL3
Tabla de contenido
loading

Este manual también es adecuado para:

30127413012742

Tabla de contenido