Seneca K-SUPPLY Manual De Instrucciones página 12

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

Fuse sizing selection
This section provides indications on the sizing of the fuse to be used for the protection
of the inputs as required by the number of boards that the K-SUPPLY module must
power.
The table below provides the sizing recommended per type of fuse for battery-powered
systems (21...30 V) in which surge is not foreseen.
Numbers of modules
2
5
10
20
35
50
70
The table below provides the sizing recommended for systems in which surge is
foreseen with 23 to 30V voltage.
Numbers of modules
2
5
10
20
35
50
70
100
Rapid type
_
_
_
750 mA
1250 mA
1600 mA
2500 mA
Rapid type
_
_
_
_
1250 mA
1500 mA
2 A
2500 mA
MI000951-E
Average type
100 mA
200 mA
400 mA
630 mA
1250 mA
1600 mA
_
Average type
_
_
_
600 mA
1 A
1250 mA
1600 mA
_
Delayed type
100 mA
200 mA
400 mA
630 mA
_
_
_
Delayed type
300 mA
300 mA
300 mA
500 mA
_
_
_
_
ENGLISH - 4/8
Tabla de contenido
loading

Tabla de contenido