STEINEL PROFESSIONAL IR Quattro COM 1 Manual De Instrucciones página 26

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 61
Functions – Settings by potentiometer
COM 1 + COM 2
Potentiometer
Twilight setting
The chosen response threshold
can be infinitely varied from
approx. 10 – 1000 lux.
Examples of use
Night-time mode
Corridors, foyers
Stairs, escalators, moving walkways
Washrooms, toilets, switchrooms, canteens
Sales fl oor, kindergartens, nursery school rooms,
sports halls
Work environments: Offi ces, conference and meet-
ing rooms, precision assembly activities, kitchens
Working areas requiring good light:
Laboratory, technical drawing, precision work
Daylight mode
Note: Depending on the site of installation, the setting may need to be corrected by 1 – 2 marks on the scale.
Brightness is measured directly at the sensor.
Potentiometer
Time setting
Stay-'ON'- time for
switching output 1
Setting 30 sec. – 30 min.
The chosen stay-'ON' time is infi-
nitely variable from a minimum
of approx. 30 sec. to a maximum
Pulse mode (except DIM)
If the dial is set to
(fully anti-
clockwise), the unit is in pulse
mode, i.e. the output is switched
'ON' for approx. 2 sec. (e.g. for stair-
IQ mode
Turned fully clockwise: The stay-
'ON' time is self-learning and
adjusts dynamically to user
Control dial turned fully clockwise:
MAX daylight mode
Control dial turned fully anti-clock-
wise: MIN night-time operation
of 30 min. Light is calibrated after
3 min. When the threshold is
exceeded, the sensor switches
'OFF' after the stay-'ON' time
expires.
well lighting timer). Afterwards,
the sensor does not respond to
movement for approx. 8 sec.
behaviour. The optimum time
cycle is determined by means of
a learning algorithm.
- 25 -
Depending on the site of installa-
tion, the setting may need to be
corrected by 1-2 marks on the
scale.
Brightness settings
min
1
2
3
4
5
>=6
max
Day mode is the only mode
possible here because of dazzle by
light from external sources.
The shortest time is 2 min.,
the longest 20 min.
Tabla de contenido
loading

Este manual también es adecuado para:

Ir quattro com 1 apIr quattro com 2Ir quattro dimIr quattro hd com 1Ir quattro hd com 1 apIr quattro hd com 2 ... Mostrar todo

Tabla de contenido