GB
General recommendations
Read these instructions carefully before using the appliance for
the first time. Keep these instructions in a safe place for future
reference.
First time of use
While the manufacturing of the heaters, oil residues adhere to the
elements. The first time of use, these residues will be burnt off,
thereby occasionally triggering fire alarms. Precautions should be
taken in order to prevent this from happening.
Area of use
The Panther 6 – 15 kW fan heaters are not intended for use other
than indoors. These heaters are appropriate for the heating of
warehouses, workshops, storage rooms, show rooms, etc.
Function
The air is carried through the heater by a fan and heated by non-
corrosive elements which are regulated by the built-in thermostat
with a range of +5 - +35°C. The air speed is adjustable in three
steps.
Switching on or off, selecting half or full output and regulating
the RPM is performed through the control panel PP15 (ordered
separately) which is wall mounted for easy access.
The appliance is protected from overheating via a built-in
temperature limiter. To reset, see Overheating.The heater is
mounted on a wall with a bracket, which allows direction of the
air stream in several directions, straight ahead, to the left, to the
right and down.
Installation
The fan heaters are intended for wall mounting. The appliance
must not be placed directly under a wall-outlet.
N.B.! The minimum distances given in fig. 2 and 3 must be kept.
The fan heaters must not be mounted on the ceiling.
• Loose the bracket from the appliance by
unscrewing the bolts.
• Mark holes by means of the loose bracket.
• Drill holes for the fixing plugs.
• Mount the bracket.
• Mount the fan heater on the bracket and adjust
the heater to desired vertical and horizontal
angles.
• Screw the bottom bolt in and tighten all bolts.
8
Panther 6 - 15 kW
Installation and Operating Instructions
Electrical installation
The electrical installation should be carried out by a qualified
electrician in conformity with prevailing regulations. The appliance
should be preceded by an all-pole switch with at least 3 mm
breaking gap. There are several ways to connect depending on
the desired function.
On delivery the appliance is equipped with connections on the
terminal block. With a con-
nection between terminals
14 and 15, the fan RPM
will be controlled by the
regulation and the heat by the thermostat. Without the connection
the thermostat will control both fan RPM and heat.
When accessories are connected or when several
heaters are connected to each other and controlled by a common
accessory, the connections are replaced according to drawings
1 – 6.
Between terminals 1 and 13, a 230V~ alarm signal can be
obtained. When the temperature limiter is triggered, the voltage
will drop to zero.
On delivery the Panther 6 – 15 fan heaters are for
400V 3N~. The heaters can be reconnected to 230V3~ according
to fig. 4.
The connection should be made with a cable type S05VV-U,
A05VV-R or similar. For control H05VV5-F0,75 mm² or similar
may be used.
Type
Output kW
All
control
SE 06
6
SE 09
9
SE 12
12
SE 15
15
SE 135
13,5
On the back of the appliance there are knock-outs.
Cable-glands used must guarantee the protection class require-
ments!
When several heaters are connected to each other and control-
led by a common accessory it should be stated in the group
centre that "The fan heaters are fed from more than one group
supply".
Safety
• Ensure that the area around the intake and
exhaust grille is kept free from material which
could prevent the air flow through the appliance.
• The appliance has hot surfaces during operation!
• The appliance must not be covered either with
clothes or similar material since overheating of
the appliance can result in a fire hazard.
Voltage V
Min.area
mm²
230V~
0,75
400V 3N~/230 V3~
1,5/2,5
400V 3N~/230 V3~
2,5/6
400V 3N~/230 V3~
4/10
400V 3N~/230 V3~
6/16
500V 3~/440 V3~
4/2,5