DESCRIPTION:
The DOMOTAX TeLeGeST PRIME d3P is a three-phase static meter for
measuring both active and reactive energy. It is directly connected to the
indoor installation, with communications capabilities and functions that
allow telemanagement.
It complies with the requirements of Directive 2014/32/UE, RD 244/2016
and ORDEN ITC/3022/2007.
"OBIS" CODE
1.18.0
DATA
000001
20-01-2017 11 : 45 : 50
1
1+2+3+
DATE AND TIME
ACTIVE QUADRANT/
ENERGY DIRECTION
PHASE PRESENCE/
CURRENT DIRECTION
Main characteristics:
1. Register
for
measuring
consumption, in import and export.
2. Register for measuring both inductive and capacitive reactive
energy consumption.
3. Six tariff periods, each with its maximum power register.
4. Two pulsed LED for active and reactive energy.
5. The equipment measures the following electrical magnitudes in any
quadrant:
- Active power
- Reactive power
- rms voltage
- rms current
φ
- Cos
THREE-PHASE STATIC METER
DISPLAY SCREEN
PLC CONNECTION
STATUS INDICATOR
ACCESSIBLE BUTTON
FOR OBTAINING ON-SCREEN
INFORMATION
SEALABLE BUTTON
FOR MANUALLY RESETTING
THE MAXIMETER
SEALABLE
SCREWS
TERMINAL COVER
DISPLAY SCREEN
PLC CONNECTION
STATUS INDICATOR
ACCESSIBLE BUTTON
FOR OBTAINING ON-SCREEN
INFORMATION
SEALABLE BUTTON
FOR MANUALLY RESETTING
THE MAXIMETER
SEALABLE
SCREWS
WIRE COVER
ACTIVE PERIOD
UNITS
T225
kWh
STATUS OF THE
BREAKER RELAY
C
1 2 3
ALARMS
COMMUNICATIONS
INDICATOR
both
active
and
reactive
6. It is fitted with three poles circuit breaker.
7. Communications may be remote (via a PLC) or local (via an optical
interface).
8. Detects and registers the opening of terminal cover or wire cover.
9. Detects and registers power supply circuit breaker operations and
resets.
INSTALLATION
The seals may only be removed by authorised personnel.
MOUNTING: The equipment is secured by means of the three holes that
form the securing triangle according to DIN 43 857, using the following
mounting dimensions:
CONNECTION
Connect according to the wiring diagram.
During wiring, it is essential to secure the wire in place using both
screws.
The power terminals accept wires up to 8 mm in diameter (from 6 to 35
2
mm
wire section) using two M8 screws.
DATA DISPLAY
Data is automatically shown on the screen. Another way to display data
is to repeatedly press the Info button.
CHANGING SUMMER-WINTER TIME
Summer-winter time changeover is automatically performed on the
official dates.
CLOSING
A time period can be closed in three different ways:
- Manually, by pressing the Close key
- By means of remote optical communications
- Automatically at the programmed time, on the programmed date of
each month.
TECHNICAL SPECIFICATIONS
Reference voltage and frequency:
Protection class:
Own consumption in voltage circuit:
Active precision class:
energy
Reactive precision class:
Active current values
- Start-up current:
- Minimum current:
- Transition current:
- Reference current:
- Maximum current:
Reactive start-up current:
LED constant:
Operating precision
Operating backup
Operating temperature:
150
1
3
4
6
7
9
L1
L2
L3
N
3x230/400 Vac
Class II
 10 VA;  2 W, in normal
operating regime, without PLC
transmission or special function
operations
Class B according to EN 50470-3
Class 2 according to EN 62053-23
40 mA for cos φ =1
0.5 A
1 A
10 A
80 A
50 mA for sin φ =1
1000 imp / kWh / kVArh
± 0.5 s/24h at 23 ºC using quartz
3 years for the lithium battery
-25 ºC to +70 ºC
10
12
50 Hz.