Masonry Chimney; Prefabricated Chimneys; Chimney Height; Wall Pass-Throughs - Jotul F 500 Instrucciones Para Instalación

Tabla de contenido
Masonry Chimneys
When installing the Jøtul F 500 into a masonry chimney
you must conform to all of the following guidelines:
• The masonry chimney must have a fireclay liner or
equivalent, with a minimum thickness of 5/8" (16mm)
and must be installed with refractory mortar. There
must be at least 1/4" (6,35mm) air space between the
flue liner and chimney wall.
• The fireclay flue liner must have a nominal size of 8" X
8", and should not be larger than 8" X 12". If a round
fireclay liner is to be used it must have a minimum
inside diameter of 6" (157mm) and not larger than 8"
(208mm) in diameter.
• If a chimney with larger dimensions is to be used, it
should be relined with an appropriate liner that is code
approved.
• The masonry wall of the chimney, if brick or modular
block, must be a minimum of 4"(106mm) nominal
thickness. A mountain or rubble stone wall must be at
least 12" (310mm) thick.
• A newly-built chimney must conform to local codes
and in their absence must recognize national
regulations. When using an existing chimney, it must
be inspected by a licensed professional chimney sweep,
fire official, or code officer, to ensure that the chimney
is in proper working order.
• No other appliance can be vented into the same flue.
• An airtight clean-out door should be located at the
base of the chimney.

Prefabricated Chimneys

If a prefabricated metal chimney is to be used it must be a
chimney type that is tested and listed for use with solid
fuel burning appliances.
That means a chimney that is tested to the following:
High Temperature (HT) Chimney Standard UL 103 for the
U.S. and High Temperature Standard ULC S-629 for
Canada.
The manufacturer's installation instructions must be
followed precisely. Always maintain the proper clearance
to combustibles as established by the pipe manufacturer.
This clearance is usually a minimum of 2" (56mm),
although it may vary by manufacturer or for certain
chimney components.

Chimney Height

Whether a masonry chimney or prefabricated metal
chimney is used it must be the required height above the
roof line.
The requirement is:
The chimney must be at least 3 feet higher than the
highest point where it passes through the roof and at least
2 feet higher than the highest part of the roof or structure
that is within 10 feet of the chimney, measured
horizontally. See figure 3, page 13.
Chimneys shorter than 14 feet may not provide adequate
draft. This could result in smoke spilling into the room from
the stove when loading the stove, or when the door is
open. In addition, inadequate draft can cause back puffing,
which is a build up of gases inside the firebox.
Other times, chimney height can create excessive draft
which can cause high stove temperatures and short burn
times. Excessive drafts can be corrected by installing a
butterfly damper. If you suspect you have a draft problem,
consult your dealer.

Wall Pass-throughs

When your installation unavoidably requires the chimney
connector to pass through a combustible wall to reach the
chimney, always consult your local building officials, and
be sure any materials to be used have been tested and
listed for wall pass-throughs.
In the U.S.
The National Fire Protection Association's publication,
NFPA 211, Standard for Chimneys, Fireplaces, Vents and
Solid Fuel Burning Appliances permits four methods for
passing through a combustible wall. Before proceeding
with any method be sure to consult with your local
building officials to discuss any local code requirements.
Common Method:
• When passing through a combustible wall to a
masonry chimney this method requires the removal
of all combustible materials from at least 12" (310mm)
around the chimney connectors proposed location.
With a 6" (157mm)round liner the minimum area
required would be 31" x 31" (792x792mm)square.
• The space is then filled with at least 12" (310mm)of brick
around a fireclay liner. Remember, the liner must be
ASTM C35 or equivalent, with a minimum wall
thickness of 5/8" (16mm).
• It is important to remember to locate the pass-through
at least 18"(457mm) from the ceiling for proper
clearance to combustibles.
• It will be necessary to cut wall studs, install headers,
and construct a sill frame to maintain the proper
dimensions and to support the weight of the brick.
• The bricks must be solid brick with a minimum of
• 3 1/4 " (83mm) thick (4" (106mm) nominal).
• Refractory mortar must be used at the junction of the
chimney and the pass-through liner. The pass-through
liner must not penetrate the chimney liner beyond the
inner surface of the chimney liner. Use extreme care
when constructing the hole in the chimney liner, the
tiles can shatter easily. See figure 4, page 13.
In Canada
In Canada the standard has been established by the
Canadian Standard Association. The installation must
conform to CAN/CSA-B365, Installation Code for Solid Fuel
Burning Appliances and Equipment. Before proceeding be
sure to consult your local building inspector.