Series SAH22A SMART Air Hood
Specifications - Installation and Operating Instructions
The SERIES SAH22A SMART Air Hood
and easy to operate air flow hood on the market. By using the included hood stand
and wireless communications to a handheld device with the Dwyer Instruments
PredictAir
application software, a single operator can balance a branch in less time
than traditional balancing teams. Besides being lighter than most traditional capture
hoods, the ergonomic design makes the Series SAH22A easy to maneuver, with
less physical stress. The rugged polypropylene base hood features patented Quad
Flow Design Technology for controlling air flow and minimizing back pressure, which
yields superior measurement accuracy. The Wi-Fi direct communication gives reliable
communication with a distance of up to 200 yards between the hood and the handheld
test instrument. The PredictAir
application software reduces the number of steps in
the air flow balancing process using Predictive Balancing's Express Balance mode.
Predictive Balancing is a method of predicting the optimal flow set point for each
register and the order in which they should be adjusted.
INCLUDED WITH THE SAH22A
1. Translucent gray SAH22A base unit with 2´ x 2´ (0.6 m x 0.6 m) opening
2. Extendable pole 2´ to 4´ (0.6 m to 1.2 m) with handheld test instrument connection
3. Installation and operating manual
4. Pole safety clamp
5. Stationary Pole Adapter
6. SAH22A travel case
7. Cable adapter to connect the SAH22A
8. Charger and cable for SAH22A and handheld test instrument
MODEL CHART
Model
Description
SAH-22-IN
SMART Air Hood
balancing instrument, 4 ft (1.2 m) extendable pole;
batteries and handheld test instrument not included (international
shipments only)
SAH-22-LB
SMART Air Hood
balancing instrument, 4 ft (1.2 m) and 12 ft (3.6 m)
extendable poles; batteries not included
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
balancing instrument is the most accurate
Balancing Instrument
24.074
13.662
SPECIFICATIONS
VOLUME FLOW
Service: Air.
Volume Flow Units: CFM, l/s, m
3
/h.
Volume Flow Ranges: Supply: 40 to 2000 CFM. (68 to 3398 m3/h); Exhaust: 80 to
2000 CFM.
Accuracy at Calibration > 40 CFM: ±3% of reading ±7 CFM*.
Accuracy for Any Diffuser > 40 CFM: ±3% of reading ±10 CFM**.
Resolution: 1 CFM (1.7 m³/h) (.5 l/s).
TEMPERATURE
Units: °C, °F, °K.
Operating Range: 40 to 140°F (4.4° to 60°C).
Storage Range: -4 to 122° F (-20° C to 50° C).
Accuracy: ±0.3% of reading (no calibration required).
RELATIVE HUMIDITY
Range: 5 to 95%.
Accuracy: ±5% of reading (no calibration required).
ABSOLUTE PRESSURE
Units: mbar, Pa.
Range: 10 to 2000 mbar.
Accuracy @ 25°C and within 300 to 1100 mbar: ±2% of reading (no calibration
required).
Power Requirements: 3.6 VDC NCR18650B MH12210 lithium ion battery, not
included, user replaceable or (4) 1.5 VDC AA alkaline batteries, not included, user
replaceable.
Housing Material: Polypropylene.
Weight: 5.75 lb (2.6 kg).
Agency Approvals: CE, FCC, IC.
*Based on calibration with Sensing Precision Calibration Fixture and Dwyer
standard diffuser.
**Based on any diffuser in the Dwyer downloadable library.
Please see Bulletin TE-SAH-SW for PredictAir
instructions.
Phone: 219/879-8000
Fax: 219/872-9057
Bulletin TE-SAH22A
24.074
13.662
5.543
90.000°
8.909
7.103
Application Software
www.dwyer-inst.com
12
Tabla de contenido
loading

Resumen de contenidos para Dwyer SMART Air Hood SAH22A Serie

  • Página 5 ™ detección y el difusor Dwyer estándar. 1,2 m (4 pies); las baterías y el instrumento manual de prueba no **Basado en cualquier difusor de la biblioteca para descarga de Dwyer. están incluidos (únicamente en envíos internacionales) SAH-22-LB Instrumento de equilibrio SMART Air Hood , postes extensibles de ™...
  • Página 6: Esquemas De Funciones

    ADVERTENCIA Las luces LED de la campana cambian de color y patrón según el estado de la batería. que no sean aire. Dwyer Instruments, Inc. no asumirá ningún Ubicación de las luces LED Color/Patrón LED Estado de la batería de litio tipo de responsabilidad por los daños que se produzcan en la unidad o que sufra...
  • Página 7: Instalación

    INSTALACIÓN Para colocar el dispositivo de mano en el poste, ajuste el dispositivo de cierre manual Armado de los accesorios en el poste tal como se muestra a continuación. Ajuste el dispositivo de mano al poste Para colocar la campana en el difusor a fin de medir el flujo de aire que necesita para utilizando el accesorio de cierre que se encuentra en la parte de atrás del dispositivo poder ser armada en el poste extensible incluido.
  • Página 8: Resolución De Problemas

    Federal de Comunicaciones, los cambios o modificaciones que • Quite toda gota de humedad utilizando un paño limpio, absorbente, que no deje no han sido expresamente aprobados por Dwyer Instruments, Inc. pueden anular la pelusas o toalla de papel antes de guardar la unidad.

Tabla de contenido