RSVCX-R
INPUT REGISTERS
3
Temperature alert flag
Temperature range limit
4
flag
5
Temperature sensor state
6—9
Actual relative humidity
10
value
Relative humidity output
11
value
Relative humidity alert
12
flag
Relative humidity range
13
limit flag
14
Humidity sensor state
15
Calculated dew point
16—20
21
Actual CO
eq value
2
22
CO
eq Output value
2
23
CO
eq alert flag
2
24
CO
eq range limit flag
2
25
CO
eq sensor state
2
26
Actual TVOC value
27
TVOC Output value
28
TVOC alert flag
29
TVOC range limit flag
30
TVOC sensor state
31—40
41
Ambient light intensity
42
Active / Standby
43
Ambient light sensor state
44—50
HOLDING REGISTERS
1
Device slave address
2
Modbus baud rate
MIW-RSVCX-R-ES-000 - 02 / 08 / 2019
TRANSMISOR MULTIFUNCIONAL
PARA HABITACIÓN
Data type
Description
Flag indicates that measured temperature is
outside set alert values. Set to '1' when the
unsigned
measured value is outside the temperature
int.
alert values defined by holding registers 13
and 14.
Flag indicates that measured temperature
is outside set range limit values. Set to '1'
unsigned
when the measured value is outside the
int.
temperature range limit values defined by
holding registers 11 and 12.
unsigned
Flag that shows if the communication with
int.
temperature sensor is lost
Reserved, return 0.
unsigned
Actual relative humidity level
int.
unsigned
Output value according to relative humidity
int.
Flag
indicates
that
humidity is outside set alert values. Set to
unsigned
'1' when the measured value is outside the
int.
Relative humidity alert values defined by
holding registers 17 and 18
Flag
indicates
that
humidity is outside set range limit values. Set
unsigned
to '1' when the measured Relative humidity is
int.
outside limit range values defined by holding
registers 15 and 16
unsigned
Flag that shows if the communication with
int.
humidity sensor is lost
signed int.
Calculated dew point
Reserved, return 0.
unsigned
CO
equivalent level
int.
2
unsigned
Output value according to CO
int.
Flag indicates that measured CO
outside set alert values. Set to '1' when the
unsigned
measured value is outside the CO
int.
values defined by holding registers 21 and
22.
Flag indicates that measured eCO2 is outside
set range limit values. Set to '1' when the
measured eCO2 is outside limit range values
set defined by holding registers 19 and 20
unsigned
Flag that shows if the communication with
int.
CO
eq sensor is lost
2
unsigned
TVOC level
int.
unsigned
Output value according to TVOC
int.
Flag indicates that measured TVOC level is
unsigned
outside set alert values. Set to '1' when the
int.
measured value is outside the TVOC values
defined by holding registers 25 and 26
Flag indicates that measured TVOC is outside
unsigned
set range limit values. Set to '1' when the
int.
measured TVOC is outside limit range values
set defined by holding registers 23 and 24
unsigned
Flag that shows if the communication with
int.
TVOC sensor is lost
Reserved, return 0.
unsigned
Measured ambient light intensity
int.
Active or Standby indication according
the Active / Standby light level defined by
unsigned
holding registers 31 and 32. If the measured
int.
light level is between the two levels the
indication is 0 (Low intensity)
unsigned
Flag that shows if the communication with
int.
the ambient light sensor is lost
Reserved, return 0.
Data type
Description
unsigned
Modbus device address
int.
unsigned
Modbus communication baud rate
int.
Data
0—1
0—1
0—1
0—1000
0—1000
measured
Relative
0—1
measured
Relative
0—1
0—1
-700—700
400—60000
equivalent
0—1000
2
level is
2
range limit
0—1
2
0—1
0—1
0—60000
0—1000
0—1
0—1
0—1
0—32 000
0—2
0—1
Data
1—247
0—6
www.sentera.eu
volver al índice
Values
0 =
Measured temperature is OK
1 =
Measured temperature is too high/ low
0 =
Temperature range is OK
1 =
Temperature range is too high/ low
0 =
1 =
1000 =
0 =
1000 =
0 =
Relative humidity range OK
1 =
Relative humidity range too low/high
0 =
Relative humidity range OK
1 =
Relative humidity range too low/high
0 =
1 =
200 =
1000 =
0 =
1000 =
0 =
Measured CO
1 =
Measured CO
eq is too high/ low
2
0 =
CO
1 =
CO
eq range is too high/ low
2
0 =
1 =
2000 =
0 =
1000 =
0 =
Measured TVOC is OK
1 =
Measured TVOC is too high/ low
0 =
TVOC range is OK
1 =
TVOC range is too high/ low
0 =
1 =
1000 =
1000 lux
0 =
Low light intensity
1 =
2 =
0 =
1 =
Default
Values
1
0 =
1 =
2 =
2
3 =
4 =
5 =
6 =
No
Yes
100,0 % rH
0 %
100 %
No
Yes
20,0°C
1000 ppm
0 %
100 %
eq is OK
2
eq range is OK
2
No
Yes
2000 ppb
0 %
100 %
No
Yes
Active
Standby
No
Yes
4.800
9.600
19.200
38.400
57.600
115.200
230.400
10 - 12