Cable Glands - Scame electrical solutions ALUBOX-EX Serie Instalación Uso Y Mantenimiento

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

ALUBOX-EX
4.3 DRILLING AREAS
D
Fig. 2
Code
653.9000
653.9001
653.9002
653.9003
653.9004
653.9005
653.9007
Table 2
4.4 PROTECTION – EARTHING
Fig. 3

4.5 CABLE GLANDS

Use only cable glands that have been approved Ex e and Ex tc IIIC.
Certified cable glands and plugs can be assembled only if their IP degree of protection is suited to the IP degree of protection of
the enclosure.
Make sure that the cable glands used are suitable for the cable so as to prevent any loosening and guarantee a permanent seal
against humidity.
Other conditions are indicated in the cable gland instructions.
MP37122
A
B
C
Top and bottom sides
A/C W1 x D1
65x38
90x38
102x41
129x57
170x69
205x96
300x117
A threaded hole is provided on an exterior wall of the enclosure,
(Fig.3), for connection to the earth conductor; use terminal
screws and the non-rotating bracket supplied with the enclosure
as indicated in the figure.
Carry out the equipotential connection between the bottom and
the cover of the box using the screws and inserts supplied as
standard equipment.
F
Right and left sides
B/D H2 x D2
48x38
78x38
88x41
114x57
140x69
192x96
236x117
12
Back wall
F H3 x W3
62x59
59x96
87x107
104x142
145x178
189x228
236x317
ZP90748-5