Elkron ITG500 Manual Del Usuario página 4

Módulo de entrada para detector 4-20ma
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

ENGLISH
O
GENERAL DESCRIPTION
Based on a microcontroller and equipped with a
short circuit isolator, the input module ITG500 is
used to connect a 4-20mA detector on
addressed fire prevention systems.
The module works is in multi-threshold mode
and the alarm thresholds are selectable by dip-
switches or through a programming performed
on
control
panel;
generation can be picked out for excess or for
deficiency for example of gas.
The ITG500 is able to store automatically, into
its non volatile memory, thirty measures before
and thirty measures after the alarm condition.
These measures can be displayed in graphic or
in text mode on the control panel monitor. This
feature is very important to understand what has
happened before and after the alarm condition
being detected.
The bi-colour LED (green-red), in operating
mode, indicates the detector condition while, in
service mode, it can be used to show the
detector's
address
activated from the control panel
For further information refer to the manual FAP
series control panel's programming manual.
The ITG500 module is comply and approved
according to the EN 54-17 and EN 54-18
standards.
on
ITG500
the
alarm
by
a
special
function
TERMINAL BOARDS
3
2
JP3
1
2
3
JP4
1
2
3
M3
1
2
Nr.
1
Shield
2
Detection circuit negative input
3
Detection circuit positive input
Nr.
1
Detection circuit positive output
2
Detection circuit negative output
3
Shield
Nr.
1
Power supply positive input 24Vdc
2
Power supply negative input
Nr.
Power supply positive output – detector
1
24Vdc
2
Power supply negative output - detector
3
4-20mA current measurement input
JP1:
Closed: detection line positive input and output
shorted together.
Open: default setting
JP2:
Closed: default setting
Open: power off module
JP3 and JP4:
Pos. 1-2: outgoing current
Pos. 2-3: incoming current; default setting
4/12
1
M4
ON
1
2
3
4
JP2
JP1
M2
M1
1
2
3
1
2
3
M1
Description
M2
Description
M3
Description
M4
Description
Tabla de contenido
loading

Productos relacionados para Elkron ITG500

Tabla de contenido