4.3 VALVE INSTALLATION
A) Introduce the valve in CLOSED position between the flange adaptors (where there have to be H dimension T 2.2).
Avoid dirty or strange elements in the gasket flat faces.
When introducing the valve, be careful of not damaging the gaskets.
B) Install the bolts, nuts and washers following the order and the torque indicated in the Fig. 5 and T 5.2.
It will be necessary to install all the bolts in the flange holes, even if they do not fix a valve hole. In other situations the valve could
not work correctly.
Is it always compulsory to use washers between flange and bolt or flange and nut.
C) Manual testing of the valve working.
Change the actuator selector handle in MANUAL position (B) MAN (Fig 6).
Open the valve turning the actuator wheel counterclockwise to the "90" position (Fig. 7). The valve must be opened without dif-
ficulty. If the opening or closing of the valve takes any inconvenience, check the Troubleshooting table (T 13)
Change again the actuator selector to (A) AUTO position (Fig 6).
Fig. 5
Fig. 6

4.4 ELECTRICAL CONNECTION

A) Check that the valve voltage indicated in the actuator label corresponds to your power supply.
B) Disassembly the power connector (GREY EN175301-803 A) to wire it following the electric diagram:
GREY PLUG
EN175301-803 FORM A
IMPORTANT: Use a wire of 8 to 10.5mm diameter and keep all the connector elements: o-rings, cable gland, etc. With a non ap-
propiate wire, the tightness degree (IP protection) could be lost.
STD ELECTRIC BUTTERFLY VALVE
VAC/VDC - 3 wires
N/(or)-
FUSE
L/(or)+
CLOSE
1
2
3
Screws and screw maximum tightening torque
T 5.2
D
DN
inch
Screws (A2)
63
50
-
4xM16x120
75
65
2 1/2"
4xM16x140
90
80
3"
8xM16x150
110
100
4"
8xM16x160
125
125
-
8xM16x170
140
125
5"
8xM16x170
160
150
6"
8xM20x200
200
200
-
8xM20x210
225
200
8"
8xM20x230
250
250
-
12xM20x270
280
250
10"
12xM20x270
315
300
12"
12xM20x310
Fig. 7
VDC - 2 wires
-
FUSE
+
OPEN
Torque
Torque
(N·m)
(inch·lbs)
25
221
25
221
25
221
30
265
35
310
35
310
40
354
50
442
50
442
80
708
80
708
80
708
CLOSE
OPEN
1
2
3
Torque
wrench
24 mm
30 mm
7