Anexo
A.1 Modbus
Offset Número
Nombre
de regis-
tros
50047 2
Active Language
50059 2
Display contrast
50061 2
Display illumination level
(normal mode)
50063 2
Display illumination level
(dimmed mode)
50065 2
Display illumination dimm
time
50067 2
I(N) Display
50069 2
Default Menu Nr
50071 2
Timeout for returning to
Default Menu
84
Formato
Unidad
unsigned long
unsigned long
unsigned long %
unsigned long %
unsigned long min
unsigned long
unsigned long
unsigned long
Rango admitido
1, 2, 4, 8
•
1 = English
•
2 = Portugese
•
4 = Spanish
•
8 = Chinese
1 ... 10
0 ... 1
•
0 = Off
•
1 = On
0 ... 1
0 ... 99
0 ... 1
•
0 = Hide I(N)
•
1 = Display calcula-
ted I(N), depends on
Hookup
DISPLAYED MENU
NUMBER:
1-12: only existing me-
nues are accepted
•
1 = MEAS_VLN
•
2 = MEAS_VLL
•
3 = MEAS_I
•
5 = MEAS_P
•
6 = MEAS_Q
•
7 = MEAS_SPQ
•
8 = MEAS_PF
•
9 = MEAS_F
•
11 = MEAS_WORK_P
•
12 = MEAS_WORK_Q
0... 3600s
•
0 = No timeout
•
10s - 3600s = ti-
meout
(1s <= timeout < 10 =
timeout is set to 10s)
Manual de producto, 05/2020, L1V30610008C-01
Acceso
a valor (software)
read only/read write
RW
RW
RW
RW
RW
RW
RW
RW
PAC1020