Rapier 48w Switch
Selecting a Site
Before you install the switch, review the following considerations about its
location.
■
The Rapier 48w switch requires an ambient temperature from 0º C to 50ºC
(32º F to 122º F).
■
There should be adequate front-to-back airflow around the switch and its
vents.
■
The site should be dust-free and without moisture.
■
Humidity can be from 5% to 80% non-condensing.
■
You need a reliable and earthed (grounded) power supply source, preferably
dedicated and filtered.
■
The switch ports are suitable for connection to intra-building or non-
exposed cabling only (NEBS requirement)
■
Cabling must not be exposed to sources of electrical noise, such as radio
transmitters, broadband amplifiers, power lines, electric motors, and
fluorescent fixtures.
■
Related network devices can be connected to the switch but cannot exceed
maximum cable lengths specified in the Hardware Reference.
■
Ensure easy access to the switch's power and cable connections.
■
You may need to remove cabinet doors to accommodate cords and cables.
■
When rack mounted, the switch must be located evenly to prevent uneven
mechanical loading of the rack.
■
Rapier 48w DC models are NEBS compatible only when the switch is
located in a network telecommunications facility.